ETC Installation Guide

Dual Tech Vacancy Sensor

Prepare for Installation

Ceiling-mount sensors are intended for installation to a finished ceiling
surface, soft ceiling tile mounted, or attached to a round or octagonal fixture
junction box.

Compliance

cULus Listed

CE compliant

For use with ETC Echo Control Systems, powered by an Echo station power
supply.

Environment

Ambient

For indoor, commercial controls use only. Operating temperature 0-40°C
(32-104°F), humidity maximum 90% (non-condensing).

Location

ETC recommends paying special attention to the installation environment:

When operating in PIR only modes, the sensor must have an
unobstructed view of the room. Do not mount behind or near tall
cabinets, shelves, hanging light fixtures, etc.

Do not install the sensor within eight feet from an HVAC airflow
duct/vent.

Install the sensor where it cannot easily sense movement in areas
outside of the intended space, such as hallways, glass partitions, or
adjacent rooms. If the installation location cannot avoid these
conditions, portions of the lens can be masked to block the sensor
view of these undesired areas. See

Lens Masking on page 10

.

Note:

In areas of increased noise activity, enabling PIR only mode

may allow for better vacancy detection results. See

DIP Switches on

page 7

.

Dual Tech Vacancy Sensor

Page 2 of 12

ETC

Содержание E-DVAC-C-LR

Страница 1: ...l The sensor relies on local station control for manual on and provides auto off functionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options...

Страница 2: ...n environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sen...

Страница 3: ...connection and to allow slack for future service needs Note ETC requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for grounding when control...

Страница 4: ...cation junction box or finished surface and strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...ll the sensor wires through the access holes to the unfinished side of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on the sensor...

Страница 6: ...y A buttons and their related LEDs are not used and have no functionality on the Dual Tech Ceiling mount Vacancy Sensor Set Space and Address Two rotary switches on the sensor electronics provide for...

Страница 7: ...are ignored Instead the settings made by the EchoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and...

Страница 8: ...o On Customization of the sensor and all actions are configured using the EchoAccess App For more detailed information about custom configuration options available using EchoAccess see the EchoAccess...

Страница 9: ...gins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period a...

Страница 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 11: ...t 3 0 m 10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6...

Страница 12: ...ETC Installation Guide Dual Tech Vacancy Sensor Dual Tech Vacancy Sensor Page 12 of 12 ETC...

Отзывы: