Overview

The Echo Dual Tech Ceiling-mount Vacancy Sensor uses passive infrared (PIR)
technology and acoustic detection to provide reliable vacancy sensing for
lighting control. The sensor relies on local station control for manual on and
provides auto off functionality upon detection of vacancy.

The ceiling-mount sensor offers 360 degree coverage with optimized lens
options to accommodate small and large spaces.

Model

Coverage m

2

Coverage ft

2

E-DVAC-C-SR

Small Room

41.8 m

2

 at 2.4 m

450 ft

2

 at 8 ft

74.3 m

2

at 6.7 m

800 ft

2

at 12 ft

E-DVAC-C-LR

Large Room

167 m

2

at 2.4 m

1,800 ft

2

at 8 ft

279 m

2

at 6.7 m

3,000 ft

2

at 12 ft

Field-installed lens masks are provided to allow customized detection fields
for each sensor lens type.

Custom Configuration

This document guides you through the installation and local DIP switch setup
of the sensor. For more detailed information about custom configuration
options available using EchoAccess, see the EchoAccess App integrated help
system.

Note:

To use the configuration settings applied using EchoAccess,

DIP switch 2 must be enabled. See

DIP Switches on page 7

.

Содержание E-DVAC-C-LR

Страница 1: ...l The sensor relies on local station control for manual on and provides auto off functionality upon detection of vacancy The ceiling mount sensor offers 360 degree coverage with optimized lens options...

Страница 2: ...n environment When operating in PIR only modes the sensor must have an unobstructed view of the room Do not mount behind or near tall cabinets shelves hanging light fixtures etc Do not install the sen...

Страница 3: ...connection and to allow slack for future service needs Note ETC requires that all stations and devices be grounded for ESD protection Pull an additional 2 5 mm2 14 AWG wire for grounding when control...

Страница 4: ...cation junction box or finished surface and strip each wire 11 mm 7 16 in 2 Temporarily remove the sensor cover to gain access to the configuration switches and mounting access holes Hold the sensor i...

Страница 5: ...ll the sensor wires through the access holes to the unfinished side of the ceiling tile 4 Secure the sensor in place a Insert the soft ceiling tile adapters through the provided pinholes on the sensor...

Страница 6: ...y A buttons and their related LEDs are not used and have no functionality on the Dual Tech Ceiling mount Vacancy Sensor Set Space and Address Two rotary switches on the sensor electronics provide for...

Страница 7: ...are ignored Instead the settings made by the EchoAccess App are used 3 and 4 Vacancy Timeout 5 min Switches 3 and 4 are Off 15 min Switch 3 is Off and Switch 4 is On default 30 min Switch 3 is On and...

Страница 8: ...o On Customization of the sensor and all actions are configured using the EchoAccess App For more detailed information about custom configuration options available using EchoAccess see the EchoAccess...

Страница 9: ...gins If the sensor does not detect occupancy again during the vacancy timeout period the lights turn off and a 30 second grace period begins Grace Period The sensor features a 30 second grace period a...

Страница 10: ...seconds 3 Move throughout the space including corners and areas that may be obscured from line of sight to the sensor Each time the sensor detects movement the lens illuminates red If acoustic detect...

Страница 11: ...t 3 0 m 10 ft 3 0 m 10 ft 4 6 m 15 ft 4 6 m 15 ft 6 1 m 20 ft 6 1 m 20 ft 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m Large Room Lens Side View 0 8 ft 2 4 m 10 ft 3 0 m 12 ft 3 7 m 0 3 0 m 10 ft 3 0 m 10 ft 6...

Страница 12: ...ETC Installation Guide Dual Tech Vacancy Sensor Dual Tech Vacancy Sensor Page 12 of 12 ETC...

Отзывы: