DRd Rack Enclosure Installation Manual
Maximum Current Draw of Racks
Short Circuit Current Rating (SCCR)
Rack Type
Phase Type
Maximum
Current Draw
Suggested
Breaker Rating
DRd6
Single Phase (1Ø)
120A
150A
Three Phase (3Ø)
80A
100A
AX6
Single Phase (1Ø)
120A
1
150A
3
Three Phase (3Ø)
80A
1
100A
3
DRd12
Single Phase (1Ø)
240A
300A
Three Phase (3Ø)
160A
200A
AX12
Single Phase (1Ø)
240A
1
300A
3
Three Phase (3Ø)
160A
1
200A
3
AX12X
Single Phase (1Ø)
480A
2
400A
4
Three Phase (3Ø)
320A
2
400A
3
N o t e :
1
Connected to DRd rack enclosure with a full complement of 20A modules.
2
Connected to two DRd rack enclosures with a full complement of 20A modules.
3
Installed in a main circuit breaker (MCB) model auxiliary rack.
4
Wire bending space limits the feed to the AX12X-MCB rack to 400A maximum.
ETC installs a 100% rated two pole breaker (or two poles from a three pole
breaker) in the AX12X-MCB, for a total deliverable current of 400A in a single
phase (split phase) configuration.
Rack Configuration
SCCR at
100-120
VAC
SCCR at
240 & 277
VAC
DRd6
22,000A
22,000A
DRd6 with AX6 rack (MCB)
100,000A
65,000A
DRd12
22,000A
22,000A
DRd12 with AX12 Main Lug rack
22,000A
22,000A
DRd12 with AX12X (cross-bussed) Main Lug rack 22,000A
22,000A
DRd12 with AX12 Main Circuit breaker
100,000A
65,000A
DRd12 with AX12X Main Circuit breaker
100,000A
65,000A