ETC Installation Guide
ArcSystem Pro Multi-Cell
ArcSystem Pro Multi-Cell
Page 5 of 24
ETC
Emergency System Overview
ArcSystem drivers and fixtures can be purchased in UL924 listed variants. Each of the fixtures can be
configured to be UL924 listed when wired into an existing emergency response system. See
Installing 100–125 V Emergency Multi-Cell Fixtures
and
Installing 100–277 V Emergency
.
Install the ArcSystem multi-cell fixture in a location that is accessible by qualified personnel for
testing of the emergency operation.
Note:
Fixtures must be hard-wired to emergency certified drivers to be considered for
UL924 certification.
Note:
Emergency fixtures must be installed in a high bay situation.
Note:
The number of designated emergency lamps and their height is the responsibility of
the specifier and installer in order to achieve the minimum FC levels of NFPA101.
Installation scenarios should be evaluated by the AHJ to confirm illuminance and
performance requirements of ANSI/NFPA 101 and the IBC.
Note:
ArcSystem Pro One-Cell Micro fixtures in emergency installations must be installed
with a maximum mounting height of 23.2 ft (7.07 m).
Note:
Installation must follow all national and local codes for electrical equipment.
Note:
Normal and emergency wiring cannot be contained in the same conduit according
to NEC 700.10(B).