Commissioning

Filling the heating system

19

7

Commissioning

7.1

Filling the heating system

Monitoring the screw joints

Due to vibration and thermal expansion, all screw
joints  must  be  inspected  and  tightened  prior  to

commissioning. 

Permissible media

Heating water according to ÖNORM H 5195-1.
The  permissible  water  hardness  for  the  heating
water can be determined from the table in Section

8 "Water hardness"

.

The requirements of ÖNORM H 5195-1 apply
as  minimum  requirements  for  the  heating

water. If stricter country-specific regulations exist,
they are to be heeded.

Water/glycol  mixtures  with  a  glycol  ratio  of
minimum 20% and maximum of 30%

Glycol  has  a  higher  viscosity  than  water.
When  admixing  glycol,  the  pumping  data

must  be  corrected  according  to  the  mixing  ratio.
Proper use includes compliance with these instruc-
tions as well as the information and labelling on the
pump.

Filling and bleeding the heating system

Fill the heating system and take note of the maximum
water  pressure.  Carefully  bleed  the  heating  system
after filling.

Bleeding before commissioning

There  is  a  bleed  screw  on  the  top  of  the  module  for
bleeding the primary side.

Fig. 7-1: Bleed screw

Bleeding the pump

The  heating  system  must  be  filled  and  bled
before the pump can be bled. The pump automat-

ically bleeds itself when starting for the first time. If it
does not, carry out the following steps.
1. If the pump is not in operation, start it manually. To

do this, carry out the following intermediate steps:
a) Up to software version X.35.X

Raise the authorisation to [Service]. Switch to
the  inputs  and  outputs  menu  in  the  function
block  of  the  heating  circuit  [I/O  menu] 

.

Select the heating circuit pump and press the
[Terminal] button. In the open window, switch
on  the  output  manually  by  pressing  the  [On]
button.

b) Software version X.36.0 and later

Raise the authorisation to [Service]. Switch to
the  inputs  and  outputs  menu  in  the  function
block of the heating circuit 

. Tap on the 

symbol on the heating circuit pump. The pump
is turned on manually with the [On] button, and
turned off by pressing the [Off] button.

2. If the pump is in operation, press the control button

on the pump for 3 seconds.

Fig. 7-2: Venting

3. The  venting  function  now  starts  and  lasts  for  10

minutes.  The  upper  and  lower  LED  rows  flash
alternately every second.

To cancel, press the control button again for 3
seconds.

After venting, the LED display shows the
operating mode of the pump that was previously

set. After bleeding, the operating mode of the pump
may need to be adjusted.

Содержание System Separation Module

Страница 1: ...2021 02 17 EN 0000000219 V 006 X 35 15 X 51 0 939003 002 System Separation Module Operating Instructions ...

Страница 2: ...ETA Heiztechnik Gewerbepark 1 A 4716 Hofkirchen an der Trattnach Tel 43 0 7734 22 88 0 Fax 43 0 7734 22 88 22 info eta co at www eta co at ...

Страница 3: ...injury DANGER On non compliance with this safety instruction there is a risk of major physical injury 1 2 Warranty guarantee and liability Requirements We can only accept liability for the function of our products if they are correctly installed and operated This is only possible if the conditions below are complied with Installation in a dry frost proof room A dry frost proof room is required for...

Страница 4: ...airs Repairs are only permitted using spare parts provided by us The only exceptions are common standardised parts such as electrical fuses or fastening materials as long as they possess the required features and do not restrict the functionality of the system Repair of defects For repairs of defects carried out by the customer or by a third party ETA shall only bear the costs or remain obligated ...

Страница 5: ...l equipment Low Voltage Directive 2004 108 EC Legislation relating to electromagnetic compatibility 2011 65 EU Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment RoHS 2 guideline Applied standards EN 60335 1 2020 Household and similar electrical appliances Safety Part 1 General requirements IEC 61000 6 1 2 2005 Electromagnetic compatibili...

Страница 6: ...imary side 10 Circuit board EM C 11 Bleed screw Dimensions Technical data Free residual pump head primary side Underfloor heating 13 kW 75 33 C 0 27 m h 7 00 mWs Radiator heating 40 kW 75 50 C 1 39 m h 3 00 mWs Free residual pump head secondary side Underfloor heating 13 kW 35 28 C 1 62 m h 2 20 mWs Radiator heating 40 kW 65 45 C 1 74 m h 1 50 mWs Connections DN20 3 4 internal thread Pump primary ...

Страница 7: ...eratures of the primary and secondary sides All components have already been connected at the factory Power is supplied via a 230 V Schuko socket Only the CAN bus connection to the ETAtouch con trol panel may be established Contact thermostats are required for underfloor and wall heating in order to protect the second ary side against overheating If the secondary side is at risk of frost an additi...

Страница 8: ...formance chart shows a flow rate of approx 1 30 m h 1 30 m h a free residual pump head of 3 5 m occurs on the secondary side with a pressure loss of approx 1 6 m Performance chart Free residual pump head 1 Pump head 2 Module pressure loss 3 Free residual pump head Primary spread Flow return Secondary spread Flow return 75 C 35 C 40 K 35 C 30 C 5 K 75 C 33 C 42 K 35 C 28 C 7 K 75 C 30 C 45 K 35 C 2...

Страница 9: ...sults in a primary side flow rate of approx 0 29 m h at 15 kW output and 45 K spread 0 29 m h a free residual pump head of 7 0 m occurs on the primary side with a pressure loss of approx 0 2 m Performance chart Free residual pump head 1 Pump head 2 Module pressure loss 3 Free residual pump head Primary spread Flow return Secondary spread Flow return 75 C 35 C 40 K 35 C 30 C 5 K 75 C 33 C 42 K 35 C...

Страница 10: ...crew joints for the secondary side The pressure gauge and ball valve on the flow and the safety valve and a ball valve on the return Include flat seals with all screw joints Fig 4 1 Screw joints for the secondary side Mount both ball valves on the primary side with the included flat seals Fig 4 2 Screw joints for the primary side Installing the piping Connect the piping from the heat producer on t...

Страница 11: ...ble open route siphon funnel so that malfunctions especially a failure of the safety valve to close can be detected In the same way the frost protection is collected when opening the safety valve and can be filled again Establishing a CAN bus connection to the boiler Establish the bus connection between the boiler and the module with the supplied CAN bus line Also see 6 2 CAN bus installation for ...

Страница 12: ...pen the system configura tion menu with the Systems configuration button Start the configuration assistant with the Starting the assistant button Description for software version X 36 0 and later The following description and screen shots represent the software interface of version X 36 0 and later Factory configuration The function blocks for the system separa tion module SSM a heating circuit HC...

Страница 13: ...s Operation below freezing point Yes or No Options Module is a consumer within an ETA system EM C 3 Heating circuit Heating circuit as underfloor heating The heating circuit pump is already contained within the system separa tion module Settings HC type Underfloor heat Heating circuit pump none Heating circuit mixing valve no Room sensor None EM C 3 Sys System Settings Outside temperature sensor v...

Страница 14: ...board Function blocks Description Circuit board Function blocks Description GM C 0 BufferFlex Buffer storage tank Settings Temperature sensor number 3 Combination tank No Consumer levels 1 Solar heating system not present Start relief for log boiler No Producers Consumers GM C 0 BufferFlex Consumer level 1 top EM C 3 SSM Prim flow EM C 3 SSM Sec flow EM C 3 HC ...

Страница 15: ...y isolated from the power supply CAUTION Flexible stranded conductors If flexible stranded conductors are not used for the wiring the contacts in the plug connections will be subjected to excessive mechanical strain In this case the warranty for the electronics would become null and void Only flexible stranded conductors may be used for the wiring 6 2 CAN bus installation Establishing a CAN bus co...

Страница 16: ...otect the consumer from feed temperatures that are too high 1 NC contact 2 NO contact 3 COM contact 4 Adjustment dial for activation temperature The contact thermostat is inserted between the circuit board terminal and the pump Fig 6 2 Connection of the contact thermostat Contact thermostat as frost protection If the secondary side is filled with frost protection because it is designed as an outdo...

Страница 17: ...ounted on the sec ondary side for overheating protection the additional contact thermostat is clamped serially to the EM C circuit board 1 Contact thermostat for primary circuit as frost protection 2 Contact thermostat for secondary circuit as overheating protection 3 Secondary pump ...

Страница 18: ...ut Free S103 230 V input Water shortage switch bridged S600 T1 Temperature input Secondary side flow temperature S600 T2 Temperature input Primary side flow temperature S600 T3 Temperature input Outside temperature sensor S600 T4 Temperature input Free S600 T5 Temperature input Free S600 T6 Temperature input Free S601 RS 485 bus Free digital room sensor S602 PWM output analogue output Free S603 PW...

Страница 19: ... Bleed screw Bleeding the pump The heating system must be filled and bled before the pump can be bled The pump automat ically bleeds itself when starting for the first time If it does not carry out the following steps 1 If the pump is not in operation start it manually To do this carry out the following intermediate steps a Up to software version X 35 X Raise the authorisation to Service Switch to...

Страница 20: ...get value H is increased linearly from H to H over the flow rate Q The differential pressure produced by the pump is set to the respective differential pres sure target value This operating mode is recommended for radiators for reducing flow noises on the thermostat valves Differential pressure constant Δp c The differential pressure is held constant at the set differential pressure target value H...

Страница 21: ...eating circuit must be adjusted by an expert on site Differential pressure variable Δp v Differential pressure constant Δp c 7 3 Concluding activities Mounting the plastic cover Reattach the plastic cover after commissioning Pull off the protective film and affix the ETA logo in the corre sponding recess ...

Страница 22: ...h a 45 kW boiler and 1000 litre total water volume 1 For the module the ratio of water content to output is less than 0 3 l kW Table 2 2 The maximum output of the module is 45 kW With a total heating water volume of 1 000 litres for example a specific water content of 22 2 l kW results average column in Table 2 3 The total output of the module is 45 kW therefore only the data from the first line 5...

Страница 23: ...5 C If 45 C has not been achieved before the lapse of the set duration Sec pump max switch on delay the secondary pump still starts up in order to supply the consumer The secondary pump is switched off when the consumer s demand has been met A maximum flow temperature can be set for the secondary side in order to protect the underfloor heating for example Underfloor heating and wall heating system...

Страница 24: ...eat producer for the module primary side 3 Primary side flow temperature 4 Primary pump and current speed 5 Flow temperature of the secondary side 6 Consumer on the secondary side A line appears if the consumer is being charged and the flow temperature and the symbol of the consumer are shown in yellow Function The heat is released from the primary side heat producer e g buffer via the heat exchan...

Страница 25: ...duration Sec pump max switch on delay the secondary pump still starts up in order to supply the consumer The secondary pump is switched off when the consumer s demand has been met A maximum flow temperature can be set for the secondary side in order to protect the underfloor heating for example Underfloor heating and wall heating systems still require a safety thermostat however ...

Страница 26: ...www eta co at ...

Страница 27: ......

Страница 28: ...www eta co at www eta co at downloads DOWNLOAD ...

Отзывы: