ETAtouch controller
[Solar] function block
61
In solar heating systems with external heat
exchangers, experience has shown that most of the
energy from the solar heating system goes to the tank
in this control principle.
5.7.5
Solar heating system with external
heat exchanger and stratified
charging valve
Solar heating system with external heat exchanger
and stratified charging valve
This variation of solar heating system also aims to
produce a sufficiently high temperature in the upper
area of the buffer, so the boiler does not have to start
for hot water charging.
Fig. 5-61: Solar heating system with external heat exchanger
and stratified charging valve
The collector pump starts as soon as the collector is
warmer than the target temperature in the upper buffer
area [Buffer target solar].
The control principle is identical to that of a buffer with
two internal coils. The conditions for solar charging into
the upper buffer coil are also the same. They are
described in chapter
5.7.3 "Solar heating system for
.
The speed control of the secondary pump is identical
to that of a solar heating system with an external heat
exchanger, see chapter
.
The only difference is the switching of solar
charging from the lower buffer coil to the upper. If
the conditions for solar charging into the upper coil are
not met, the lower coil will be charged first. If the
secondary feed temperature rises enough that the
temperature in the upper buffer area [Buffer top Solar]
is exceeded, solar charging is immediately switched to
the upper coil. There is no minimum time for solar
charging. Once the secondary feed temperature drops
below the temperature [Buffer top Solar], the lower coil
is again charged.
The secondary flow temperature rises when the
collector temperature increases or the speed of
the secondary pump decreases.
Содержание PelletsCompact33-50 kW
Страница 1: ...2017 04 19 EN 0000000285 V 003 3 38 0 2703 93120 002 PelletsCompact 33 50 kW Operation...
Страница 27: ...ETAtouch controller Getting to know the control system 27...
Страница 31: ...ETAtouch controller Boiler function block PelletsCompact 33 50 kW 31...
Страница 41: ...ETAtouch controller Buffer function block 41...
Страница 45: ...ETAtouch controller Hot water tank function block 45...
Страница 49: ...ETAtouch controller Fresh water module function block 49...
Страница 63: ...ETAtouch controller Solar function block 63...
Страница 67: ...ETAtouch controller Pellet store function block 67...
Страница 74: ...www eta co at...
Страница 75: ......
Страница 76: ...www eta co at www eta co at downloads DOWNLOAD...