18

www.eta.co.at

Adjusting software parameters

Fuel change

5.2

Adjusting software parameters

Setting the [Service] access level

For setting some parameters, the [Service] access
level is required. 

To set this access level, press [Toolbox] 

 in the

overview screen.

Next, press [Change authorisation]. A window opens.

Enter the password "135" and press [Log in] to confirm.

5.2.1

Fuel

Explanation [Fuel]

This parameter sets the type of fuel used. The control
system contains appropriate values for each type of
fuel, to ensure optimum combustion and ash removal.

This parameter is factory-set to [Woodchips].

Changing the parameter

Press [Boiler] to select the function block.

Press 

 to go to the function block's text menu. The

parameter is at:

Select the parameter and press [Change]. 

A settings window opens:

Make your selection and press [Accept] to save.

If the fuel is set to [Pellets] or [Miscanthus], the
setting for flue gas recirculation is automatically

changed to [Yes]. 
If the fuel is [Woodchips], the [No] setting is made au-
tomatically.

If you know the water content and density of the
fuel you are using, you must also adjust these two

parameters. You can find them in the same submenu.

Changing the de-ashing interval

Open the settings by pressing the 

 button in boiler

overview. A settings window will open. Select the
desired parameter in this. Enter the new value and
press [Accept] to save.

The de-ashing interval can also be changed in the 
text menu. The parameters can be found under:

The de-ashing interval may only be modified after
consultation with a specialist or ETA customer

service.

5.2.2

Flue gas recirculation

Explanation of [Flue gas recirculation]

When the fuel setting is changed in the control system,
the status of the flue gas recirculation is adjusted auto-
matically. 

If the fuel is set to [Pellets] or [Miscanthus], the
setting for flue gas recirculation is changed to

[Yes]. 
If the fuel is [Woodchips], the setting is [No]. 

However, if wood chips with less than 15% water
content are used, the [Yes] setting must be made

manually.

Checking the setting

The current setting can be checked in the [Boiler]
function block's text menu at:

Boiler

Settings

Fuel

Boiler

Ash removal

De-ash after min.

De-ash after max.

Boiler

Settings

Flue gas recirculation

Содержание HACK 200

Страница 1: ...2015 02 06 EN 0000000135 V 002 X 29 0 93706 Flue Gas Recirculation HACK 200 kW Installation...

Страница 2: ...ETA Heiztechnik Gewerbepark 1 A 4716 Hofkirchen an der Trattnach Tel 43 0 7734 22 88 0 Fax 43 0 7734 22 88 22 info eta co at www eta co at...

Страница 3: ...djusting the gearbox motor 11 4 3 Installing the drive chain 12 4 4 Adjusting the shutoff device 14 4 5 Installing the flue gas pipe 14 5 Fuel change 16 5 1 Overview 16 5 2 Adjusting software paramete...

Страница 4: ...Individual configurations depicted or described here are only optionally available In the event of contradictions between individual documents regarding delivery scope the information in our current...

Страница 5: ...thus The combustion temperature increases significantly with these fuels resulting in an increased risk of slag formation and wear in the boiler Recirculating the flue gas from the boiler outlet back...

Страница 6: ...6 www eta co at Overview 3 Overview 1 Flue gas pipe 2 Turbulator 3 Flue gas duct 4 Chain protector 5 Cover...

Страница 7: ...re seal 5 M8 x 235 threaded rod 6 M8 x 30 hexagonal long nut 7 Flue gas duct 8 Fibre glass seal 9 Self locking M8 hexagonal nut 10 Hexagonal screw M8 x 35 11 Drive shaft stub 12 Guard plate 13 Rear si...

Страница 8: ...8 www eta co at Overview Flue gas pipe 1 Hexagonal screw M5 x 16 2 Silicon foam seal 3 Insulation...

Страница 9: ...annot be switched back on and verify that it is safely isolated from the power supply Preparations 1 Remove the precut recess on the back wall and cut out the insulation 2 Remove the cover behind the...

Страница 10: ...Mount the flue gas duct on the boiler with four M8 x 30 hex long nuts The flue pipe opening is at the top 2 Glue the ceramic fibre seal to the flue gas duct flange 3 Screw the four M8 x 235 threaded...

Страница 11: ...Adjusting the gearbox motor 1 Remove the guard plate from the drive motor by removing two M5 x 8 round head screws 2 Remove the M8 x 16 hex screw the washer the activation plate and the short spacer f...

Страница 12: ...tighten the rear of the chain protector to the flange bearing with three M5 x 12 hex screws 2 Make sure you insert a key in the drive shaft stub Grease the drive shaft stub 3 Place the drive chain on...

Страница 13: ...til the drive chain has lateral play of max 5 mm 7 Tighten the four M8 hex nuts on the threaded rods and check the chain tension again Mounting the cover 1 Place the chain protector on the rear side o...

Страница 14: ...removing four M5 x 16 hex screws 2 Place the seal of the shutoff device on the flange Rotate the shutoff device and install it with four M5 x 16 hex screws 4 5 Installing the flue gas pipe 1 Thread th...

Страница 15: ...the connection between the flue gas pipe and flue gas duct with heat resistant silicon 4 Mount the cover on the chain protector and boiler with seven M5 x 12 hex screws and washers 5 Place the insulat...

Страница 16: ...16 www eta co at Overview Fuel change 5 Fuel change 5 1 Overview...

Страница 17: ...kg 35 kg 18 kg 35 kg 10 kg De ash after max 230 kg 173 kg 155 kg 78 kg 155 kg 78 kg 155 kg 78 kg 155 kg 78 kg 80 kg 24 kg De ashing interval boiler without buffer storage tank Software parameters De a...

Страница 18: ...f you know the water content and density of the fuel you are using you must also adjust these two parameters You can find them in the same submenu Changing the de ashing interval Open the settings by...

Страница 19: ...e sensor is behind the front cover of the boiler Fig 5 1 Firebed level sensor The different positions for boilers with the stoker on the left side are described below For a boiler with the stoker on t...

Страница 20: ...www eta co at...

Отзывы: