2012-10
Troubleshooting Diagnosis
ETAbox Operation
Troubleshooting
Diagnosis
Problem/malfunction
Possible causes
Solution
Discharge conveyor's drive
motor doesn't start or runs
intermittently
• The boiler is not controlling the
motor correctly or the cables
have been attached to the motor
incorrectly
• Obstruction of attachment
nozzles on fuel conveying system
• Incorrect motor protection
setting
• Foreign object got into tank
before or during filling and is
blocking the conveyor screw
• Check motor wiring; see installation
instructions for ETAbox and boiler
• Obstruction; see "Clearing
obstructions" or "Removing foreign
objects"
• Set motor protection correctly in
boiler's control system
2.1 A nominal current and
3.0 A maximum current.
(note motor data)
• See "Removing foreign objects"
Obstruction of attachment
nozzles on fuel conveying system
• Pellet hoses leak
• Conveyor screw transports too
many pellets
• Leak in pellet bin on boiler
• Non-return flap in pellet bin on
boiler is dirty. (ETA boilers have
no non-return flap in the pellet
bin)
• Check hoses and clamps (loose hose
clamps...)
• Reduce feed rate (drive motor
speed).
"Feed rate" parameter in boiler
control system's "Store" function
block (see boiler's operating
instructions)
• Check tightness of all connecting
flanges on pellet bin
• Clean dust and pellet residues from
non-return flap
Then see "Clearing obstructions"
Conveyor screw stops moving
• Drive motor ran too long without
vacuum motor; pellets clog the
suction nozzle
• Foreign object in the screw
• See "Clearing obstructions"
• See "Removing foreign objects"
ETAbox has worked without
malfunctions for a long time, but
now no pellets are reaching the
boiler
• ETAbox is empty
• ETAbox is almost empty
• Fill with pellets
• Knock on hopper or stir the pellets
with a long rod through an
inspection port; refill