ETA-ECM20, ETA-ECM20M SPECIFICATIONS
General
Type
Power Conditioner Suppressor Module
Power Requirements
120V 60Hz
Power Consumption
.5W
RoHS Compliant
Yes
Safety Listings
MET (UL 1449 Code)
Panel
Switched Outlets
Two, 20A
Spike & Surge Suppression
H-N, N-G, H-G
Manual Override
Slide switch
Extreme Voltage Shutdown
ETA-ECM20M Model only, (EVS) Below 102V or
Above 132V AC Line (When Used With ETA-ECS6RM)
Connectors
5 Position Phoenix Euro Block Style
Fuse Protection
20A Slow Blow
DCV Remote Trigger
5–24VDC
Remote Trigger
SPST Contact
Status Signals
Output for Voltage and Current Data
(ETA-ECM20M model only)
Indicators
Incoming AC, Active, AC Fault
(ETA-ECM20M model only)
AC Mains Interconnect
Screw terminal block
Technical Data
Current Rating
15 amps
Operating Voltage
102-132 VAC
High Voltage Surge Protection
Trigger at 133 VAC, 1ms typically (When Used With
ETA-ECS6RM) (ETA-ECM20M model only)
Spike & Surge Suppression
H-N, N-G, H-G
Low Voltage Protection
Trigger 101 VAC, 1ms typically (When Used With
ETA-ECS6RM) (ETA-ECM20M model only)
Spike Protection Modes
Circuitry on incoming AC Mains.
Minimum Spike Clamping Voltage
460 VRMS @ 3,000 amps
Maximum Spike Clamping Voltage
6000V
Maximum Spike Clamping Response Time
1 nanosecond
Spike Clamping Voltage @ 100A
1250Vp for 20µs
Maximum surge current
6,500 amps
Energy Rating @ 2ms
600 Joules
Noise Attenuation EMI/RFI Sequencer
10 dB @ 10 kHz, 40 dB @ 100 kHz, 100 dB @ 10 MHz
(ETA-ECM20M model only)
Temperature Range
5º to 35º C
Humidity Range
5% to 95% R.H.
Mechanical
Chassis Finish
Black
Mounting
#8 5/16” self tapping screws
Dimensions
3.0" H x 8.5" L x 3.5" W (7.6cm x 21.6 cm x 8.9cm)
Unit Weight
ETA-ECM20=1.25 lbs(.68 kg),
ETA-ECM20M=1.75lbs (.80kg)
ETA-RACEWY6