Issue 6: No Voltage Reading at the ETA-ECS6RM.
Possible Cause #1
Check Issues 1 - 4 first.
Possible Cause #2
Proper Channel is not selected for viewing.
Possible Cause #3
Channel Activation LED is Illuminated Green but the Voltage display is not on. Check the wiring between the
ETA-ECS6RM Channel and the ECM module. “V”, “A” and “D” must be in the correct polarity.
Issue 7: No Current Reading at the ETA-ECS6RM, meter reads ‘nA’.
Possible Cause #1
An ETA-ECM20 Module is connected. This module does not support current read out.
Possible Cause #2
Check Issues 1 - 4 first.
Possible Cause #3
Current Draw of ECM Module must exceed 500mA to register.
Possible Cause #4
Proper Channel is not selected for viewing.
Possible Cause #5
Channel Activation LED is Illuminated Green but the Current display reads “nA”. Check the wiring between
the ETA-ECS6RM Channel and the ECM module. “V”, “A” and “D” must be in the correct polarity.
ETA-20SH
AC Power Conditioning & Suppression Module