background image

4

Electrical Connection

To properly install your range, you must determine the type of 
electrical connection you will be using and follow the instructions 
provided for it here.

Range must be connected to the proper electrical voltage 
and frequency as specified on the model/serial number rating 
plate. The model/serial number rating plate is located on the 
oven frame behind the storage drawer panel. Refer to the 
figures in the “Product Dimensions” section of the “Location 
Requirements” section.

This range is manufactured with the neutral terminal 
connected to the cabinet. Use a 3-wire, UL listed, 40- or 
50-amp power supply cord (pigtail) (see Range Rating chart 
below). If local codes do not permit ground through the 
neutral, use a 4-wire power supply cord rated at 250 volts, 
40 or 50 amps and investigated for use with ranges.

*The NEC calculated load is less than the total connected load 

listed on the model/serial rating plate.

**If connecting to a 50-amp circuit, use a 50-amp rated cord with 

kit. For 50-amp rated cord kits, use kits that specify use with a 
nominal 1

³⁄₈

" (34.9 mm) diameter connection opening.

A time-delay fuse or circuit breaker is recommended.

The range can be connected directly to the fused disconnect 
(or circuit breaker box) through flexible or nonmetallic 
sheathed, copper or aluminum cable. See “Electrical 
Connection.”

Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that 
the range can be moved if servicing is ever necessary.

A UL listed conduit connector must be provided at each end 
of the power supply cable (at the range and at the junction 
box).

Wire sizes and connections must conform with the rating of 
the range.

The wiring diagram is located on the back of the range or 
inside the storage drawer in a clear plastic bag.

If connecting to a 4-wire system:

This range is manufactured with the ground connected to the 
cabinet. The ground must be revised so the green ground wire of 
the 4-wire power supply cord is connected to the cabinet. See 
“Electrical Connection.”

Grounding through the neutral conductor is prohibited for new 
branch-circuit installations (1996 NEC); mobile homes; and 
recreational vehicles, or an area where local codes prohibit 
grounding through the neutral conductor.

When a 4-wire receptacle of NEMA Type 14-50R is used, a 
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power 
supply cord (pigtail) must be used. This cord contains 4 copper 
conductors with ring terminals or open-end spade terminals with 
upturned ends, terminating in a NEMA Type 14-50R plug on the 
supply end. 

The fourth (grounding) conductor must be identified by a green or 
green/yellow cover and the neutral conductor by a white cover. 
Cord should be Type SRD or SRDT with a UL listed strain relief 
and be at least 4 ft (1.22 m) long.

The minimum conductor sized for the copper 4-wire power 
cord are:

40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding

If connecting to a 3-wire system:

Local codes may permit the use of a UL listed, 3-wire, 250-volt, 
40- or 50-amp range power supply cord (pigtail). This cord 
contains 3 copper conductors with ring terminals or open-end 
spade terminals with upturned ends, terminating in a NEMA Type 
10-50P plug on the supply end. Connectors on the appliance end 
must be provided at the point the power supply cord enters the 
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.

INSTALLATION INSTRUCTIONS

Unpack Range

1. Remove shipping materials, tape and protective film from 

range. Remove oven racks and parts package from inside 
oven.

2. Do not remove the shipping base at this time.

Range Rating*

Specified Rating of 
Power Supply Cord Kit 
and Circuit Protection

120/240 Volts

120/208 Volts

Amps

8.8 - 16.5 KW
16.6 - 22.5 KW

7.8 - 12.5 KW
12.6 - 18.5 KW

40 or 50**
50

4-wire receptacle (14-50R)

3-wire receptacle (10-50R)

WARNING

Excessive Weight Hazard

Use two or more people to move and install range.

Failure to do so can result in back or other injury.

A. Shipping base

A

Содержание RF265LXTB

Страница 1: ...potential hazard is tell you how to reduce the chance of injury and tell you what can happen if the instructions are not followed Your safety and the safety of others are very important We have provid...

Страница 2: ...m beyond the bottom of the cabinets Cabinet opening dimensions that are shown must be used Given dimensions are minimum clearances The floor anti tip bracket must be installed To install the anti tip...

Страница 3: ...he ground path is adequate Do not use an extension cord Be sure that the electrical connection and wire size are adequate and in conformance with the National Electrical Code ANSI NFPA 70 latest editi...

Страница 4: ...be revised so the green ground wire of the 4 wire power supply cord is connected to the cabinet See Electrical Connection Grounding through the neutral conductor is prohibited for new branch circuit...

Страница 5: ...nt anti tip bracket to wood floor drill two 3 2 mm holes at the positions marked on the bracket template Remove template from floor To mount anti tip bracket to concrete or ceramic floor use a 4 8 mm...

Страница 6: ...e cover from range 3 Add strain relief Style 1 Power supply cord strain relief Remove the knockout for the power supply cord Assemble a UL listed strain relief in the opening Tighten strain relief scr...

Страница 7: ...t the neutral center wire to the center terminal connector using one of the hex washer head screws Securely tighten screw for proper electrical connection 5 Connect the other 2 wires lines 1 and 2 to...

Страница 8: ...icles In an area where local codes prohibit grounding through the neutral 1 Remove the ground link screw from the range frame Save the ground link screw and cup washer Bend the ground link away from t...

Страница 9: ...secure the range to the floor Any method of securing the range is adequate as long as it conforms to the standards in the Location Requirements section LevelRange 1 Place rack in oven Place level on...

Страница 10: ...ualified technician MovingtheRange When moving range slide range onto cardboard or hardboard to avoid damaging the floor covering If removing the range is necessary for cleaning or maintenance For pow...

Страница 11: ...11 ANTI TIP BRACKET TEMPLATE Cut on dotted lines and place the left edge against the left side cabinet and the top edge against the rear wall Left edge Top edge...

Страница 12: ...W10141166A 2007 All rights reserved 7 07 Printed in U S A...

Отзывы: