SAN Annunciator Manual
5
LOAD vs. DISTANCE IN FEET
SAN-CPU POWER FEED CIRCUIT
(2.4 VOLT DROP)
Current
(Amps)
#18 AWG
#16 AWG
#14 AWG
.25
738
1200
1846
.50
369
600
923
.75
246
400
615
1.00
184
300
462
1.25
148
240
369
1.5
123
200
308
1.75
105
171
263
2.00
92
150
231
2.25
82
134
206
2.50
74
120
185
2.75
67
109
167
3.00
62
100
154
3.25
57
93
142
3.50
53
86
133
Installation
Caution:
Disconnect power before removing or installing this module.
The SAN-CPU requires 1/2 module footprint. The SAN-CPU is
mounted on the back plane of the SAN-4 and SAN-8 enclosures. When
using an RSAN-6, the SAN-CPU mounts on a special “L-SHAPED”
bracket, perpendicular to the other SAN option modules installed in the
rack.
Field Wiring
TB1-1 + 24 VDC
TB1-2 24 VDC Common
P1
Ribbon Cable to SAN Option Modules.