background image

EST I

NTERNATIONAL

Issue 5

Literature Sheet #85001-0269

Page 3 of 4

Standard Detector Base, SIGA-SB, SIGA-SB4

Typical Wiring

The detector mounting bases accept #18 AWG (0.75mm

2

), #16 (1.0mm

2

),  #14 AWG (1.5mm

2

), and #12 AWG (2.5mm²) wire sizes.

Note: Sizes #16 AWG (1.0mm

2

) and #18 AWG (0.75mm

2

) are preferred for ease of installation.  See Signature Loop Controller catalog

sheet for detailed wiring requirement specifications.

Relay Detector Base, SIGA-RB, SIGA-RB4

Test Fire

Type of Detector

SIGA-IS Ion

SIGA-PS Photo

SIGA-HRS and

SIGA-HFS Rate-of

-Rise/Fixed Temp.

SIGA-PHS

Photo/Heat 3D

SIGA-IPHS

Ion/Photo/Heat 4D

Open Wood

optimum

unsuitable

optimum

very suitable

optimum

Wood Pyrolysis

suitable

optimum

unsuitable

optimum

optimum

Smouldering Cotton

very suitable

optimum

unsuitable

optimum

optimum

Poly Urethane Foam

very suitable

very suitable

suitable

very suitable

optimum

n-Heptane

optimum

very suitable

very suitable

optimum

optimum

Liquid Fire without

Smoke

unsuitable

unsuitable

optimum

very suitable

very suitable

Isolator Detector Base, SIGA-IB, SIGA-IB4

Application

Although photoelectric detectors have a wide range of fire sensing capabilities they are best suited for detecting slow, smoldering fires.
The table below shows six standard test fires used to rate the sensitivity of smoke and heat detectors. The table indicates that no single
sensing element is suited for all test fires.

EST recommends that this detector be installed according to latest recognized edition of national and local fire alarm codes.

From Power Supply

or Previous Sounder Base

DATA IN (-)

DATA OUT (-)

From Signature Controller
or Previous Device

To Next Sounder Base or

E-O-L Relay

To Next Signature Device

DATA IN (+)

24 VDC IN (+)

24 VDC OUT (+)

24 VDC IN (-)

24 VDC OUT (-)

DATA OUT (+)

DA

T

A

(+)

IN/OUT

DA

T

A

(-)

IN

DA

T

A

(-)

OUT

SIG

+

JW1

JW2

SIG

-

Jumper JW2
OUT = Steady Tone
IN = Temporal Tone

Jumper JW1
OUT = Low Volume
IN = High Volume

Audible Detector Base, SIGA-AB4

Term Description

1

Not Used

2

DATA IN/OUT (+)

3

Not Used

4

DATA IN (-)

4

Remote LED (-)

5

Remote LED (+)

6

Not Used

7

DATA OUT (-)

CONTACT RATING
1.0 Amp @ 30 VDC

(Pilot Duty)

Term Description

1

Normally Open

2

DATA IN/OUT (+)

3

Common

4

DATA IN (-)

4

Not Used

5

Normally-Closed

6

DATA OUT (-)

Term Description

1

Not Used

2

DATA IN/OUT (+)

3

DATA IN (-)

4

Not Used

5

Not Used

6

DATA OUT (-)

7

Not Used

Содержание SIGA-PS

Страница 1: ...istoryLog AutomaticDeviceMapping Stand aloneOperationandFast StableCommunication Self diagnostics and History Log Each Signature Series detector constantlyrunsself checkstoprovideimportantmaintenance information The results of the self check are automatically updated and permanently stored in the detector s non volatile memory This information is accessible for review any time at the control panel...

Страница 2: ...lative to the changing baseline This is called differential sensing Sensitivity Range The SIGA PS Photoelectric Detector has a sensitivity range or window of 0 67 to 3 77 The installer selects the detector s ALARM sensitivity level from five available settingswithintherange Pre Alarm Thedetectorstoresoneof20pre alarmsensitivityvalues to alert local personnel prior to the sensor reaching a full eva...

Страница 3: ...GA IB SIGA IB4 Application Although photoelectric detectors have a wide range of fire sensing capabilities they are best suited for detecting slow smoldering fires The table below shows six standard test fires used to rate the sensitivity of smoke and heat detectors The table indicates that no single sensing element is suited for all test fires EST recommends that this detector be installed accord...

Страница 4: ...A PS Intelligent Photoelectric Detector UL ULC Listed 5 23 Accessories SIGA SB Detector Mounting Base Standard 2 09 SIGA SB4 4 inch Detector Mounting Base c wSIGA TS4 TrimSkirt SIGA RB Detector Mounting Base w Relay SIGA RB4 4 inch Detector Mounting Base w Relay c wSIGA TS4 TrimSkirt SIGA IB Detector Mounting Base w Fault Isolator SIGA IB4 4 inch Detector Mounting Base w Fault Isolator c wSIGA TS4...

Отзывы: