Flue Stabilizer
A flue stabilizer can be fitted to reduce the draught through the stove if
the flue draught is too high.
The flue stabilizer should be;
•
fitted in the same room as the stove,
•
the same size as the flue pipe, and
•
fitted no closer than 700mm to the flue outlet of the appliance.
In
stalling the stove
Fig:
4
Clearances from combustibles
Positioning
Figure 4 shows recommended distances between the stove and surrounding
combustible materials. As a rule, any surrounding combustible material should
not exceed 80°C. There should be sufficient space around the stove for service
work.
Hearth
The construction of the hearth must conform to Building Regulations, must be
firm, non-combustible and capable of supporting the stove. The hearth must be
fire proof to at least 50 degrees Centigrade. Relevant Building Regulations
relating to hearth should be observed. The minimum hearth thickness is 13mm.
Over The Stove
7
Clearances in mm
Side
400
Rear
400
Top
450
Front
305