CABINET GROUNDING INFORMATION
Bonding and grounding should be done in accordance with the operating
telephone company’s standard procedures and comply with local electrical
codes.
GROUND WIRE
The ground wire protects the electronics from voltage surges. A #6 ground wire must be
properly grounded to provide lightning surge protection for the cabinet. Please follow
this practice for attaching the ground unless local policies dictate otherwise.
For safety and performance reasons it is imperative that a cabinet be properly
grounded. The following guidelines should be used to ground the cabinet unless
local practices, rules, or regulations dictate otherwise.
Each door and equipment rack is grounded to the cabinet frame. The cabinet frame is
connected to the internal grounding bus by a stranded wire. A similar ground wire must
be used to connect the ground bus to each equipment ground lug. These ground wires
may need to be removed temporarily to troubleshoot ground faults. The wire may be
removed by unscrewing the screws that secure the green wire to the ground bus.
Be sure to reattach these wires after troubleshooting and resolving any ground
conflicts.
Ground the cabinet before connecting power to the cabinet. This grounding
must be in effect at all times to safeguard personnel.