LED Indication
4
Connection Diagram
!
Test and Maintenance
TESTING THE DETECTOR
1.
Apply power to the detector.
2.
Wait for 30 sec.
3.
Introduce artificially generated heat directly beneath
the detector. Within 8 sec the detector will enter into fire
condition. Both LEDs will illuminate.
4.
Power off the detector for 2 sec minimum. After
resetting the detector will enter into duty mode and both
LEDs will extinguish.
SERVICE MAINTENANCE
1. Inspection for visible physical damage - weekly.
2. Operational test in real conditions - monthly.
3. Check and clean dust contamination - six months.
4. Check and clean base and head contacts and
connections - annually.
CLEANING AND MAINTENANCE
1.
Remove the detector from its base
.
2.
Remove the inner protective cover
-
press the four
clips
(1)
with a plain screwdriver
gently down to unlock
the cover from
the
dete
c
tor
’s
body.
3.
Dismount the PCB from the supporting clips (2).
4.
Clean the chamber
.
5.
Mount the PCB back to the detector’s body
-
as a
reference point use the side with a cut-out (3). Rotate the
PCB until the cut-out coincides with the pin on the inner
part from the detector body. Gently press the PCB down
to fix in place.
6.
Mount the inner protective cover
-
the mark with a
rectangular shape (4) fits with the channel at the inner
side of the detector’s body and the contact plates on the
PCB coincide with the four openings on the protective
cover. Press gently down until a click is heard.
7.
Mount the detector back to its base and test for correct
operation and LED indication.
!
Maintenance
3
1
2
Base MAGPRO-DB
Address Programming
Down
Right
Up
Modify
Esc
Enter
MAGPRO
PROG
You may also program the
address directly from the
fire panel.
Blink
ing
10
sec
OK
Light on
Light o
ff
Light on
Light o
ff
1. Blinking is enabled
2. Blinking is disabled
The LED indication can be enabled/ disabled
from the control panel.
Fire Panel
Earth
(Earth point)
RI
(Remote
indicator)
+Loop
-Loop
-Loop
(Negative Loop Wire)
+Loop
(Positive Loop Wire)