4
Specifications and Dimension
Test conditions:
Heating conditions: Ambient dry bulb / wet bulb temperature7
℃
/6
℃
Room dry bulb / wet bulb temperature20
℃
/15
℃
Cooling conditions: Ambient dry bulb / wet bulb temperature35
℃
/24
℃
Room dry bulb / wet bulb temperature27
℃
/19
℃
Fresh Air Heat Pump only handles fresh air.
HPERV-300/V2, HPERV-400/V2 Fresh Air Heat Pump (Air conditioner)
RA
filter
OA
filter
Con-
troller
box
Specifications Unit
HPERV-300/V2
HPERV-400/V2
Rated cooling capacity
W
2000
2300
Rated heating capacity
W
2500
2800
Rated cooling power
W
550
630
Rated cooling current
A
2.6
3.0
Rated heating power
W
610
685
Rated heating current
A
2.9
3.3
Maximum operating power
W
750
800
Maximum operating current
A
3.6
3.8
Power type
/
220V~50Hz 220V~50Hz
Fresh air/Exhaust air capacity
m3/h
300/220/150
400/320/240
External static pressure
Pa
80
80
Noise dB(A)
35
37
Outlet dimension
mm
184
184
Condensation drainage dimension
inch (BSP)
1/2"
1/2"
Machine overall dimension (length/
with/height)
mm 810*600*870
810*600*870
Packing dimension (length/width/
height)
mm 866*662*986
866*662*986
Net/Gross weight
Kg
92/110
92/110
Refrigerant
/
R410A R410A