Visual indication devices (VIDs), such as strobes, can be ceiling or wall mounted. 

For wall mounting they should always be mounted 2.1m above floor level. Visual 

alarm devices should conform to BS EN 54-23.

Unless MICC cable is used, all cabling should be mechanically protected from 

floor level up to a height of 2m.

EN54-23 specifies that the VAD produces an illumination of 0.4 lux on surfaces 

perpendicular to the direction of the light emitted from the device. They are 

not designed to wake people that are asleep and can be red or white light. 

VADs are classified into three categories based on their application:

W

 - Wall-mounted

C

 - Ceiling-mounted

O

 - Open Category

Wall and Ceiling mounting categories are specified at specific installation heights 

and particular patterns of coverage - see diagrams. For W and C categories, 

the shape of the volume covered is fixed by the standard. The dimensions of 

this coverage volume are specified by the manufacturer. For all categories, the 

volume covered can be used to determine VAD spacing within the building. Open 

category allows manufacturers to specify the coverage shape and volume and 

does not put any restriction on mounting height.

Wall-mounted VADs cover a cuboid 

volume with a square floor area. The 

coverage volume is presented as a 

code in the form of 

W-X-Y

, where W is 

Wall-mounted, X is the max mounting 

height (m) and Y is the width and 

length (m) of the coverage floor area. 

The min mounting height is 2.4 m.

E.g. : 

W-2.4-12 

means it should be

mounted at 2.4m from the floor and 

will cover an area of up to 12 by 12m.

Ceiling-mounted VADs cover a 

cylindrical area. The coverage volume 

is presented as a code in the form  

C-X-Y, where C is Ceiling-mounted, X 

is the max mounting height (m) and 

Y is the diameter (m) of the coverage 

volume’s floor area. The max mounting 

height can only be specified as 3, 6 or 

9m.

E.g. : 

C-3-15

 means it can be mounted 

up to 3m from the floor and will cover a 

cylindrical area of least 15m diameter.

Wall-Mounted - Coverage Volume

Ceiling-Mounted - Coverage Volume

VISUAL INDICATION DEVICES

VISUAL ALARM DEVICE CATEGORIES

>2.1m

2m

T

T

Y

Y

X

X

Содержание BS5839

Страница 1: ...www es p u k com BS5839 PART 1 2017 A GUIDE TO FIRE ALARM SYSTEMS DESIGN AUTHORISED DISTRIBUTOR Birmingham Call 0121 359 5387 Cannock Call 01543 271362...

Страница 2: ...L4 P1 P2 CATEGORIES FireAlarmandFireDetectionsystemsarecategorised in the following way P AFD designed to primarily protect property P1 AFD installed throughout all areas P2 AFD Installed only in defi...

Страница 3: ...ual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore the individual coverage can be represented by a square measuring 7 5 x 7 5m giving an actual a...

Страница 4: ...Detectors must not be sited less than 1m from air inlets or air conditioning units A device should not be mounted within 500mm of any obstruction If the top of a solid partition is less than 300mm fr...

Страница 5: ...stalled at the highest point The distance to adjacent devices can be increased by 1 per degree of angle of the roof up to a maximum of 25 Detector Type Ceiling Height m General Limits Maximum Heat RoR...

Страница 6: ...lement of a heat detection device thermistor should not be less than 25mm below ceiling and not greater than 150mm below ceiling The sensing element of a smoke detection device photoelectric smoke cha...

Страница 7: ...ion All manual call points should be fitted with a protective cover which is moved to gain access to the frangible element MANUAL CALL POINTS MCP A person should not have to travel more than 45m along...

Страница 8: ...reduced to 60dB A in stairways enclosures up to 60m and specific points of limited extent Sounder device cabling should be arranged so that in the event of a fault at least one sounder will remain ope...

Страница 9: ...the manufacturer For all categories the volume covered can be used to determine VAD spacing within the building Open category allows manufacturers to specify the coverage shape and volume and does no...

Страница 10: ...onal built in sounder allowing the whole system to be installed using only one pair of wires per zone That means easier faster installations AND cost savings 2 Wire Fire Alarm System FIRE DETECTION AL...

Страница 11: ...n still be transmitted to devices from either end of the loop Although conventional fire alarm system cost less to purchase they are generally more expensive to install This is due to each zone for de...

Страница 12: ...th the recommendations of BS5839 1 FREE SYSTEM DESIGN ESP can offer a team of dedicated design engineers who are fully trained qualified in all of the relevant British Standards We are able to provide...

Страница 13: ...dustrial Estate Dublin Ireland Tel 353 1 5577 290 Fax 353 1 2811 224 sales espi ie www espi ie Here at ESP we offer free training aimed at electrical contractors and wholesalers who would like to add...

Отзывы: