Never mount devices closer than twice the depth of light fittings.

Voids less than 800mm in height need not have independent coverage, unless 

fire or smoke is able to spread from one area to another through the void or risk 

assessment shows AFD (Automatic Fire Detection) to be necessary.

For ceilings that feature an apex: as long as the height of the apex from the 

rest of the ceiling is less than 150mm for heat detectors or less than 600mm 

for smoke detectors then these can be treated the same as flat ceilings. For 

higher apexes, a device should be installed at the highest point. The distance to 

adjacent devices can be increased by 1% per degree of angle of the roof up to a 

maximum of 25%.

Detector Type

Ceiling Height (m)

General Limits

Maximum

Heat RoR

9.0

10.5

Heat Fixed

7.5

12.5

Point Smoke Detector

10.5

12.5

Aspirating Smoke Detection Class C with 5 holes

15

18

Aspirating Smoke Detection Class C with 15 holes

25

28

Aspirating Smoke Detection Class B with 5 holes

40

43

Optical Beam Normal Sensitivity

25

28

Optical Beam Enhanced Sensitivity

40*

43

*Supplemented detection recommended unless risk of stratification is minimal.

SMOKE DETECTORS

100mm

<200mm

(500mm for detectors)

Light fitting

>800mm

Apex < 150mm

Heat Detector

Standard Spacing

Extended Spacing

Apex < 600mm

Smoke Detector

Apex > 150mm

Heat Detector

Apex > 600mm

Smoke Detector

Содержание BS5839

Страница 1: ...www es p u k com BS5839 PART 1 2017 A GUIDE TO FIRE ALARM SYSTEMS DESIGN AUTHORISED DISTRIBUTOR Birmingham Call 0121 359 5387 Cannock Call 01543 271362...

Страница 2: ...L4 P1 P2 CATEGORIES FireAlarmandFireDetectionsystemsarecategorised in the following way P AFD designed to primarily protect property P1 AFD installed throughout all areas P2 AFD Installed only in defi...

Страница 3: ...ual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore the individual coverage can be represented by a square measuring 7 5 x 7 5m giving an actual a...

Страница 4: ...Detectors must not be sited less than 1m from air inlets or air conditioning units A device should not be mounted within 500mm of any obstruction If the top of a solid partition is less than 300mm fr...

Страница 5: ...stalled at the highest point The distance to adjacent devices can be increased by 1 per degree of angle of the roof up to a maximum of 25 Detector Type Ceiling Height m General Limits Maximum Heat RoR...

Страница 6: ...lement of a heat detection device thermistor should not be less than 25mm below ceiling and not greater than 150mm below ceiling The sensing element of a smoke detection device photoelectric smoke cha...

Страница 7: ...ion All manual call points should be fitted with a protective cover which is moved to gain access to the frangible element MANUAL CALL POINTS MCP A person should not have to travel more than 45m along...

Страница 8: ...reduced to 60dB A in stairways enclosures up to 60m and specific points of limited extent Sounder device cabling should be arranged so that in the event of a fault at least one sounder will remain ope...

Страница 9: ...the manufacturer For all categories the volume covered can be used to determine VAD spacing within the building Open category allows manufacturers to specify the coverage shape and volume and does no...

Страница 10: ...onal built in sounder allowing the whole system to be installed using only one pair of wires per zone That means easier faster installations AND cost savings 2 Wire Fire Alarm System FIRE DETECTION AL...

Страница 11: ...n still be transmitted to devices from either end of the loop Although conventional fire alarm system cost less to purchase they are generally more expensive to install This is due to each zone for de...

Страница 12: ...th the recommendations of BS5839 1 FREE SYSTEM DESIGN ESP can offer a team of dedicated design engineers who are fully trained qualified in all of the relevant British Standards We are able to provide...

Страница 13: ...dustrial Estate Dublin Ireland Tel 353 1 5577 290 Fax 353 1 2811 224 sales espi ie www espi ie Here at ESP we offer free training aimed at electrical contractors and wholesalers who would like to add...

Отзывы: