PAGE 3 OF 4
EMERGENCY DRIVER
INSTRUCTIONS
Wiring
1.
The ESL-EMG-2DC requires an unswitched AC power supply of 120-277 VAC, 50/60Hz.
2.
The ESL-EMG-2DC and AC driver must be on the same branch circuit. Ensure the output current of the AC
driver does not exceed 5A.
3.
Refer to the wiring diagram below or contact factory for additional information or help.
Wiring Configuration
++
LED DRIVER
LED
-
N
L
LED LOAD
LED (+)
LED (
-
)
N
LL
SW LIVE IN
SW LIVE OUT
+ RED
-
WHITE
ON
ESL-EMG-2DC
E M E R G E N C Y
L E D D R I V E R
SELV
BATTERY
OUTPUT
TO LED
FROM LED
DRIVER
+
-
+
-
+
-
BATTERY
+ RED
-
BLACK
RED (+)
WHITE (
-
)
LED TEST SWITCH
N
L DRIVER (SWITCHED)
SWITCH
HOT
L EMERGENCY (UNSWITCHED)
ESL-EMG-2DC
Terminal block with external battery pack, choosing the different combination of the DIP switches and the
corresponding battery pack to have different ESL-EMG-2DC models with different emergency power outputs.
BATTERY MOUNTING BOX (OPTIONAL)*
*Contact factory for information
ON
OFF
1
OFF
ON
OFF
ON
OFF
OFF
ON
ON
5W
9W
15W
25W
9.6V, 1.5AH
10.8V, 2.1AH
10.8V, 3.8AH
14.4V, 4.5AH
ESL-EMG-2DC-5W
ESL-EMG-2DC-9W
ESL-EMG-2DC-15W
ESL-EMG-2DC-25W
2
MODEL
POWER
BATTERY
Copyright © 2018 ESL Vision, LLC. All rights reserved. Rev: 08/15/2018