P/N 1036525-EN • REV F 

Wiring 

Figure 6: 500N Series two-wire wiring 

 

Caution: 

Risk of system failure. The system may not operate if 

the detector is not connected to the control unit initiating device 
circuit as specified in the detector or control unit literature. 

 

Note: 

The 500N Series two-wire detectors are polarity 

sensitive. 

Note: 

CleanMe is enabled by wiring units in reverse polarity. 

Figure 7: 500N Series four-wire wiring 

 

Note: 

The 500N Series four-wire detectors are not CleanMe compatible. 

Figure 8: 500N series four-wire E model wiring 

 

Note: 

The 500N Series four-wire detectors are not CleanMe compatible. 

Model

521NB/521NBXT
521NCSXT
521NC/521NCXT

CleanMe

Enabled

CleanMe
Disabled

CleanMe
Disabled

Two-wire

initiating

circuit

First
detector

Listed alarm control

Last
detector

EOL
device

NC

COM

NO

Model

521NB/521NBXT
521NCSXT
521NC/521NCXT

Model

521NB/521NBXT
521NCSXT
521NC/521NCXT

+

_

 

Listed alarm control

Power

Initiating

circuit

First
detector

COM

NO

COM

NO

Last
detector

NC

COM

NO

Model
541NB
541NBXT

Model
541NCSRXT
541NCSRH
541NCRXT

EOL device

ESL
204-12/24V
Power
Supervision

Relay

Listed alarm control

Power

Initiating
circuit

First

detector

COM

NO

COM

NO

Last

detector

NO

COM

NC

Model
541NB
541NBXT

Model
541NCSXTE
541NCXTE

EOL device

Содержание 500N Series

Страница 1: ...r needs to be replaced This feature is available on the 500N Series two wire detectors only The 500N Series two wire detectors enable the CleanMe function by recognizing voltage polarity at installati...

Страница 2: ...etectors specified for existing construction are required and in addition a smoke detector is required in each bedroom Are more smoke detectors desirable The required number of smoke detectors might n...

Страница 3: ...on the mounting base See Figure 4 b Insert the smoke detector into the base and turn clockwise approximately 15 degrees It should snap firmly into place 7 Apply power and test the detector See Smoke...

Страница 4: ...E model wiring Note The 500N Series four wire detectors are not CleanMe compatible Model 521NB 521NBXT 521NCSXT 521NC 521NCXT CleanMe Enabled CleanMe Disabled CleanMe Disabled Two wire initiating cir...

Страница 5: ...If the error persists replace the unit 4 to 7 Unit is within normal sensitivity range N A 8 to 9 Unit is becoming too sensitive Verify that the optical chamber is snapped down securely Clean the unit...

Страница 6: ...it Unvented fire tends to build up considerable pressure Be sure all members of the household realize and understand this danger Use your neighbor s phone or a street fire alarm box to call the fire...

Страница 7: ...re 4 Four wire Product ordering Model Description Alarm current mA Reverse polarity mA 521NB Two wire photoelectric 6 5 to 20 VDC S09A 20 521NBXT Two wire photoelectric 6 5 to 20 VDC fixed temperature...

Страница 8: ...5 noncondensing Field wiring size 12 to 24 AWG 16 to 22 AWG recommended Electrical boxes Fits standard single gang and 3 1 2 in and 4 in round ceiling electrical boxes Heat detector Rate of rise Fixed...

Отзывы: