background image

2 / 8 

 

P/N 1036525-EN • REV F 

Compatibility 

Please refer to the 

ESL Compatibility Index

 for a complete 

listing of control panels and proper identifiers. For a copy of the 
compatibility index, see “Contact information” on page 8. 
Remember, four-wire smoke detectors do not require a 
compatibility listing. 

Selecting a location 

Selecting a suitable location is critical to the operation of 
smoke detectors. This equipment should be installed in 
accordance with NFPA 72. Figure 1 shows required and 
additional locations. 

Figure 1: Detector location 

 

(1) Dining 

Room 

(2) Kitchen 
(3) Living 

Room 

 (4) 

Bedroom 

(5) TV 

Room 

(6) Basement 

 Required 

smoke 

detectors 

  Additional alarms required for new construction 

Where to locate the required smoke detectors in existing 
construction. 

The major threat from fire in a family living unit 

occurs at night when everyone is asleep. The principal threat 
to persons in sleeping areas comes from fires in the remainder 
of the unit. Therefore, a smoke detector is best located 
between the bedroom areas and the rest of the unit. In units 
with only one bedroom area on one floor, the smoke detector 
should be located as shown in Figure 1-A. 

In family living units with more than one bedroom area or with 
more than one floor, more than one smoke detector is 
required, as shown in Figure 1-B. 

In addition to smoke detectors outside of the sleeping areas, 
the installation of a smoke detector on each additional story of 
the family living unit, including the basement, is required. 
These installations are shown in Figure 1-C. The living area 

smoke detector should be installed in the living room or near 
the stairway to the upper level, or in both locations. The 
basement smoke detector should be installed in close 
proximity to the stairway leading to the floor above. Where 
installed on an open-joisted ceiling, the alarm should be placed 
on the bottom of the joists. The alarm should be positioned 
relative to the stairway to intercept smoke coming from a fire in 
the basement before the smoke enters the stairway. 

Where to locate the required smoke detectors in new 
construction. 

All of the smoke detectors specified for existing 

construction are required and, in addition, a smoke detector is 
required in each bedroom. 

Are more smoke detectors desirable? 

The required number 

of smoke detectors might not provide reliable early warning 
protection for those areas separated by a door from the areas 
protected by the required smoke detectors. For this reason, it 
is recommended that the householder consider the use of 
additional smoke detectors for those areas for increased 
protection. The additional areas include the basement, 
bedrooms, dining room, furnace room, utility room, and 
hallways not protected by the required smoke detectors. The 
installation of smoke detectors in kitchens, attics (finished or 
unfinished), or garages is not normally recommended, as these 
locations occasionally experience conditions that can result in 
improper operation. 

Note: 

Regulations pertaining to smoke detector installation 

vary from state to state. For more information, contact your 
local fire department or local authority having jurisdiction. 

Additional considerations. 

In addition to NFPA 72, use the 

following location guidelines to optimize performance and 
reduce the chance of false alarms from the detector: 

• 

Locate ceiling-mounted smoke detectors in the center of a 
room or hallway at least 4 in. (10 cm) from any walls or 
partitions. 

• 

Locate wall-mounted smoke detectors so the top of the 
alarm is 4 to 12 in. (10 to 31 cm) below the ceiling. 

• 

Do not 

locate detectors in or near bathrooms or kitchens. 

• 

Locate smoke alarms in a suitable environment with 
temperature and humidity as defined in “Specifications” on 
page 8. 

• 

Locate smoke detectors away from air conditioners, 
heating registers, and any other ventilation source that 
may interfere with smoke entering the alarm. 

• 

Mount smoke detectors on a firm, permanent surface. 

Installing the detector 

All wiring must conform to the National Electric Code (NEC) 
and/or local codes having jurisdiction. Use 12 to 24 AWG (16 
to 22 AWG recommended) wire to install the detector. 

1.  If you are using the detector-base lock, remove the 

detector knockout and break off the tab on the mounting 
base. See Figure 2. 

2.  Remove the red plastic cover from the detector. The 

detector is shipped with a cover for protection against 
construction site dust. 

(1)

(2)

(3)

(4)

(4)

(4)

(1)

(2)

(3)

(4)

(5)

(4)

(4)

(4)

(4)

(3)

(1)

(6)

A

B

C

Содержание 500N Series

Страница 1: ...r needs to be replaced This feature is available on the 500N Series two wire detectors only The 500N Series two wire detectors enable the CleanMe function by recognizing voltage polarity at installati...

Страница 2: ...etectors specified for existing construction are required and in addition a smoke detector is required in each bedroom Are more smoke detectors desirable The required number of smoke detectors might n...

Страница 3: ...on the mounting base See Figure 4 b Insert the smoke detector into the base and turn clockwise approximately 15 degrees It should snap firmly into place 7 Apply power and test the detector See Smoke...

Страница 4: ...E model wiring Note The 500N Series four wire detectors are not CleanMe compatible Model 521NB 521NBXT 521NCSXT 521NC 521NCXT CleanMe Enabled CleanMe Disabled CleanMe Disabled Two wire initiating cir...

Страница 5: ...If the error persists replace the unit 4 to 7 Unit is within normal sensitivity range N A 8 to 9 Unit is becoming too sensitive Verify that the optical chamber is snapped down securely Clean the unit...

Страница 6: ...it Unvented fire tends to build up considerable pressure Be sure all members of the household realize and understand this danger Use your neighbor s phone or a street fire alarm box to call the fire...

Страница 7: ...re 4 Four wire Product ordering Model Description Alarm current mA Reverse polarity mA 521NB Two wire photoelectric 6 5 to 20 VDC S09A 20 521NBXT Two wire photoelectric 6 5 to 20 VDC fixed temperature...

Страница 8: ...5 noncondensing Field wiring size 12 to 24 AWG 16 to 22 AWG recommended Electrical boxes Fits standard single gang and 3 1 2 in and 4 in round ceiling electrical boxes Heat detector Rate of rise Fixed...

Отзывы: