front of and behind the product. While assembling to adjacent elements, pay attention that no oppression force shall be applied on the 
housing  and  the  mounting  components  (bolts,  o-rings,  sliders)  must  be  suitable  for  the  geometry  and  working  conditions  of  the 
equipment. No changes should be made on the product (drilling, grinding, soldering etc.). To avoid exceeding usage limits (PS, TS), make 
sure that the inlet side is protected with a suitable device. Sufficient buffer volumes should be left at the line outlet after the device, 
before installation. Confirm the accuracy of the bumper volume on the outlet side. The buffer volume should be 1/500 of the flowrate 
at pressures up to 300 mbar and 1/1000 at higher pressures. 

Check the accuracy of the flow direction.  See the arrow mark on the body. Vent and relief lines, which may be required, must be made 
in accordance with applicable rules and laws.  In  mountings made with non-condensing gases, the product can be assembled in any 
position.  In mountings with condensed gases such as LPG, the product should be placed at horizontal or vertical flow direction and the 
outlet side should be downwards. Installation should be carried out with appropriate and approved seals. The sealed surface should be 
clean and soft and new seals should be used at all times. Clean the inner side of the entire pipeline where the product will be installed 
with compressed air before mounting the product and take precautions to ensure that these lines will not be contaminated again. Make 
sure there are no particles left at any point on the line (dust, dirt, sawdust, foreign particles etc.). The fluid that will flow to the product 

must be filtered before the product. A filter with ≤ 50 μm

 pore width should be placed at the inlet side.  The regulator and SSD should be 

kept away from direct sunlight and corrosive atmospheric effects. 

The said pressure equipment must be installed in a non-seismic area and should not be exposed to fire and lightning strikes. For outdoor 
installations, the regulator must be located away from vehicle traffic and positioned so that water, ice and other foreign substances do 
not enter the spring case through the ventilation hole. Avoid placing the regulator under fringes or down pipes. Make sure that it is above 
the potential snow level.  Check the risk of explosive mixture in the pipeline. Make sure that all valves used before and after the product 
which provide gas flow to the product are closed. Before starting the mounting, ensure that there is no pressure gas trapped in the line 
where the product will be installed and between the line and the product, that the gas supply is turned off and that the possibility of 
opening  is  completely  prevented.  Prevent  explosive  gas-air  mixture.  Avoid  contact  voltage  and  ignition  of  sparks  in  the  product. 
Necessary measures shall be taken to ensure that there is no sound and vibration caused by the line. Before installation, take appropriate 
measures (clamping at the line side etc.) at the line inlet and outlet to reduce bending and torsion loads caused by pipes and shocks. 
Attention should be paid to the relevant limitations in counter forces and moments caused by pipes and connections.  

Make sure that the necessary dimensions and areas are provided considering further operations (testing, maintenance, disassembly etc.). 
In any case, check that the inlet pressure of the product shall be higher than the outlet pressure. Ensure that there are no diameter 
narrowing and expansion over short distances at the inlet and outlet of the line on which the product will be mounted. Before installation, 
it should be checked and ensured that the line pressure is within the inlet pressure range specified on the label on the product and that 
the product capacity will not be exceeded during operation. It should be checked and ensured that there is no damage on the product 
(visual and functional), that the product to be installed is suitable for the system to be used, that the pressure does not exceed the 
maximum pressure level specified on the product label, that the product's dimensions fit with the line, that the installation place is at 
adequate distance and under protection so that it will not be affected by sparks and electrical currents that may be caused by flammable 
substances and devices. 

Proceed with the installation process by taking necessary measures (such as protection box etc.) so that the product will not be exposed 
to direct external environmental, corrosion and wearing conditions (sun, atmosphere, rain, snow, humidity, water, external chemicals 
etc.) and to potential external damages and impacts. If the products are to be used in floor-mount applications, this should be indicated 
while placing the order. In this case, products with properly coated surfaces should be used and appropriate measures should be taken 
to prevent dirt, dust, dirt, liquid, etc. at the discharge part, if any, of the product. In addition, it should be ensured that the products shall 
not be in form of embedded in full or in part into water, soil or liquids. If requested during order placing, the regulator may be equipped 
with a breath line for leaking into the atmosphere as a result of a failure (such as diaphragm failure). If necessary (e.g., the use of the 
product indoors etc.), the exhaust line must be connected to the breath line console of the product. This connection must be threaded 
with  minimum  DN10  screws.  The  threaded  screw  adapter  required  for  this  connection  shall  be  requested  and  used  from  the 
manufacturer and shall be used accordingly. Gas pressure regulators and SSDs with discharge system; shall not be installed and operated 
in closed areas and floor-mount applications without taking necessary measures for transmitting the gas to be discharged to the safe 
zone (e.g. transmitting and mixing the gas to be discharged with a pipe of minimum DN 10 to external atmospheric conditions, etc.). 
Before installing the product on the line; perform a general check for the pressure and sealing of the line and system. 

B. DURING MOUNTING 

Manually remove the inlet-outlet connection protection plugs, if any. If the product is equipped with modular connection additionally, 
manually and carefully place the inlet and outlet seals which are shipped in the product box to the inlet and outlet connection nozzles 
(always use certified and new seals). Set the flow direction of the product by showing the arrow outlet side and gas flow direction in the 
product body and ensure that the joint components to be used during installation shall comply with the regulations. Install the product 
only in accordance with applicable legislations and local regulations, obtaining the necessary approvals, if necessary. Do not install the 
product outdoors without mounting the product into a housing and taking required protective measures. The lifting equipment being 
used must be suitable for loads to be lifted. While connecting the product to the line no overload, force and impact shall be applied.

  

Содержание ERG-H5

Страница 1: ...sactions Save for Future Requirements Products must only be authorized by authorized persons This product must be installed in accordance with applicable rules and guidelines ESKA VALVE A Sakarya 1 Or...

Страница 2: ...plement the right systems to protect the product Taking into considerations the factors such as tampering the product unauthorized opening of the product covers inserting wires water dirt etc and othe...

Страница 3: ...DEFINITIONS AND ABBREVIATIONS Device or Product ESKA Brand Gas Pressure Regulator SSD Automatic Safety Shut Off Device Authorized Body Gas distribution company existing in the province or region wher...

Страница 4: ...te of 200 m3 h and input pressure below 5 bar in connections with input from above through inside gas consumption devices which are placed after gas meters used in homes and similar places Permissible...

Страница 5: ...sed as a backup inspection device and is spring driven The ERG H5 Model gas pressure regulator has a high and or low pressure gas safety shut off device that is built in the same body i e placed in an...

Страница 6: ...in the product and the box as well as the documentation manual warning label certificate etc which have to be available with the product In case of deficiencies or failures please contact the manufact...

Страница 7: ...shall be higher than the outlet pressure Ensure that there are no diameter narrowing and expansion over short distances at the inlet and outlet of the line on which the product will be mounted Before...

Страница 8: ...s use a gland or ball valves at the product inlet and outlet Connect the product to the line without causing mechanical stress It should be remembered that excessive loads to be applied to the body ma...

Страница 9: ...roduct is not reverse mounted After the product is assembled carry out the necessary checks Ensure that the product impermeability is provided example external impermeability visual control Gas Inlet...

Страница 10: ...leased gas is mixed in the atmosphere if the product is equipped with a discharge system and check that outlet and gas impermeability is achieved by appropriate methods foam detector etc 7 Wait until...

Страница 11: ...anizations should be contacted immediately If the product is closed for various reasons during operation the inlet and outlet valve should be closed the problem should be detected and the product shal...

Страница 12: ...struction 8 Monitor the output pressure from the manometer and bring it to the set value and make sure that the slam shut remains installed at the desired value OUTER LEAKAGE TEST 1 Set the inlet pres...

Страница 13: ...ssure increase is achieved in clockwise rotations and pressure decrease in reverse rotations 6 If there is an SSD an increase in safety pressures should be ensured when adjusted output pressures are i...

Страница 14: ...been exceeded All aforementioned tests should be repeated and it shall be ensured that the results are in conformity It is recommended to seal the adjustment devices so that the settings are not chan...

Страница 15: ...n 2 Cleaning and protection of the pipeline before the product in general after commissioning maintenance may be required very often since the pipeline is not clean enough 3 The level of reliability r...

Страница 16: ...spring supplied from the manufacturer properly and without forcing 4 Place the H1 TEMPER NUT No 9 with the appropriate hexagonal wrench to its initial position 5 Manually assemble the SR UPPER COVER P...

Страница 17: ...duct In all cases make sure that nobody is present indoors in any situation which leads to gas release from the product or the line to the atmosphere that no hazardous atmosphere is and or will be for...

Страница 18: ...nsions are in mm Figure 9 Regulation Discharge No 1 G1 4 ISO 228 SSD Discharge No 2 G1 8 ISO 228 SSD Sensing Line No 3 GE12 1 4 For Pipes 12 X 1 5 Regulation Sensing Line No 4 GE12 1 4 For Pipes 12 X...

Страница 19: ...Page 19 of 32 Figure 11...

Страница 20: ...Page 20 of 32...

Страница 21: ...5 C 1013 mbar Q n m h natural gas x K Q n m h x gas Example Q n m h natural gas x 0 78 Q n m h air Correction factor K at 15 C Butane 0 55 Propane 0 64 Oxygen 0 76 Air 0 78 Nitrogen 0 81 Biogas 0 85 C...

Страница 22: ...ight to make changes in the spring settings Please contact the spring manufacturer Internal Sensing Active Internal and External Sensing Active Pd Outlet Pressure bar Maximum Capacities m3 h Natural G...

Страница 23: ...not lift during transportation In case of repacking no humidity or wetness shall remain in the product The product shall be stored in environments which are isolated from forces such as falling tippin...

Страница 24: ...g to the type of problem if you do not prefer to carry out these procedures or if you have despite the performance of such procedures not solved the problem or have not remedied the suspicion of a pro...

Страница 25: ...odel The dimensions of the gas line may be incorrect Increase the nominal width of the pipeline The gas filter before the regulator may be contaminated Carry out maintenance on the gas filter replace...

Страница 26: ...ealed do not perform this process The product line connection may not be fully connected If there is a leak in the outlet connection nozzle remove the product from the line remove the outlet seal manu...

Страница 27: ...s which may cause combustion cigarettes lighters matches etc extinguish all open fires and smoky substances sources that may create sparks and fires do not re start Do not touch turn on or off any ele...

Страница 28: ...rihi 01 11 2020 The name of the Notified Body and No Onaylanm Kurulu un Ad ve Numaras T V NORD System GmbH Co KG 0045 EU Conformity Assessment Method AB Uygunluk De erlendirme Y ntemi 2014 68 EU PED C...

Страница 29: ...name of the Notified Body and No Onaylanm Kurulu un Ad ve Numaras T V NORD System GmbH Co KG 0045 EU Conformity Assessment Method AB Uygunluk De erlendirme Y ntemi 2014 68 EU PED Category I Modul A2 M...

Страница 30: ...gineering Practice SEP Declaration Deklarasyon We declare that our products with a serial number as defined above meet the requirements 2014 68 EU PED Pressure Equipment Directive Article 4 item 3 The...

Страница 31: ...4 84 E mail info eskavalve com Authorized Signature Authorized Stamp THE SELLER S Title Address Phone Fax E mail Authorized Signature Authorized Stamp COMMODITYS S Type Gas Pressure Regulator Brand ES...

Страница 32: ...ing free repairs and in cases where the goods have failed again within the warranty period the maximum period for repair has been exceeded it has been identified by the authorized service station sell...

Отзывы: