When there's no flow in the 
regulator, the output pressure 
rises. 
And 
Output pressure in the 
regulator is constantly 
increasing 

Orifice may be damaged. 

Change the orifice 

Flap may be damaged 

Change the flap. 

Main diaphragm may be damaged 

Change the main diaphragm. 

The sealing area in the body is contaminated 

Clear the relevant fields. 

The regulator valve plug may not be installed. An internal 
leak may be possible. 

Check the regulator valve plug, change it. 

 

 

Fluctuation in output pressure 
of the regulator. 

Possible friction in the balancing mechanism. 

Clean the components of the balancing mechanism. 

Traction below minimum capacity. 

Increase the flowrate or change the regulator model. 

The plug cap of the regulation top cover may not be 
attached. 

Put the cap on. 

Output pressure in the 
regulator increases during 
flow. 

The main diaphragm may be damaged. 

Change the main diaphragm. 

Constant output pressure 
increase in the regulator. 
And 
Leaking in regulator when Q=0 

Regulator valve plug may not be installed. Potential 
internal leak. 

Check the regulator valve plug. If necessary, replace. 

Orifice and/or class may be defective. 

Check the regulator orifice and the flap. Replace or contact 
the manufacturer. 

O-rings may be damaged 

Change the o-rings. 

Operation or Balancing Diaphragm may be defective. 

Change the Operation or Balancing Diaphragm. 

There may be contanination or foreign objects in the 
sealed area. 

Clean the sealed area. 

The obturator may be damaged. 

Replace. 

The output pressure drops 
constantly. 

Possible external leak. 

Find the leak and seal it. Replace the relevant part or contact 
the manufacturer. 

No gas flow in regulator 

Possible icing due to humidity. 

Check for freezing of the water which may ingress into the 
line or the product. 

Connections may not be fully tightened. 

Check for loose connections or screws, if yes, tighten 
according to the rules. (if the screws are sealed do not 
perform this process) 

Filter may be clogged. 

Remove the product from the line, manually remove and 
clean the line filter before the product, install the new filter 
properly manually if necessary and make sure it is fully 
seated, mount the product back to the line 

The product's SSD may have turned off. 

Try re-installing the product. 

The problem may not have been detected. 

Replace the product with a new one. 

External leak in the product 

Connections may not be fully tightened. 

Check for loosened connection or screw and tighten 
according to the rules. (if the screws are sealed, do not 
perform this process) 

The product-line connection may not be fully connected. 

If there is a leak in the outlet connection nozzle, remove the 
product from the line, remove the outlet seal manually, if 
there is no visual problem, install it back in, reassemble the 
product to the line 

The operation diaphragm may be damaged. 

Change the operation diaphragm. 

The drain valve may be contaminated. 

Clean the drain valve. 

High output pressure in the 
regulator which is outside the 
tolerances 

Possible error in the line pressure. 

Stop the gas traction at the outlet, close the inlet valve, then 
turn it on and re-activate the product and check the result. 

The output adjustment pressure may be set incorrectly. 

Measure output adjustment pressure and correct if incorrect. 

The problem may not have been detected. 

Replace the product with a new one. 

Discharge system errors in 
regulator 

The discharge adjustment spring may be loose. 

Tighten or replace the spring. 

The discharge gasket may be contaminated. 

Replace the discharge gasket. 

Possible mechanical jam  

Replace with a new product. 

Insufficient flowrate in 
regulator 

Product selection may be incorrect. 

Check that the wrong product is not selected in terms of flow 
rate and output pressure. 

The line and filter may be contaminated. 

Take measures for line cleaning. Replace the filter.  

Input pressure may be too low. 

Measure input pressure and check that it is not below the 
minimum input pressure. 

The output adjustment pressure may be set incorrectly. 

Measure output adjustment pressure and correct if incorrect 

The problem may not have been detected. 

Replace with a new product 

Missing accessories in the 
product 

There may be missing accessories in the product. 

Identify missing parts such as the cocking lever plastic, 
pressure adjustment seals, if any, discharge protection plug if 
any, discharge filter if any, etc., request these parts from the 
manufacturer and install new parts manually. 

Sound and vibration in the 
product 

The mounting position may be incorrect. 

Check if the mounting position is correct. 

Possible fluctuation in input pressure. 

Check for fluctuations in input pressure. 

There may be diameter defects in the output pipeline. 

Check for undesirable diameters and similar narrowing at the 
outlet side 

SSD general errors 

The SSD lever may be damaged or defective. 

Check the SSD lever for impact marks and bending. 
Try to re-install the product. 
Replace with a new product. 

Sudden interruption of use 

Check if there is any pressure increase due to abrupt stop of 
outlet flow, combi boiler, boiler etc. 

There may be a narrowing of the diameter in the outlet 
line. 

Check the outlet line for excessive diameter contraction. 

Содержание ERG-H5

Страница 1: ...sactions Save for Future Requirements Products must only be authorized by authorized persons This product must be installed in accordance with applicable rules and guidelines ESKA VALVE A Sakarya 1 Or...

Страница 2: ...plement the right systems to protect the product Taking into considerations the factors such as tampering the product unauthorized opening of the product covers inserting wires water dirt etc and othe...

Страница 3: ...DEFINITIONS AND ABBREVIATIONS Device or Product ESKA Brand Gas Pressure Regulator SSD Automatic Safety Shut Off Device Authorized Body Gas distribution company existing in the province or region wher...

Страница 4: ...te of 200 m3 h and input pressure below 5 bar in connections with input from above through inside gas consumption devices which are placed after gas meters used in homes and similar places Permissible...

Страница 5: ...sed as a backup inspection device and is spring driven The ERG H5 Model gas pressure regulator has a high and or low pressure gas safety shut off device that is built in the same body i e placed in an...

Страница 6: ...in the product and the box as well as the documentation manual warning label certificate etc which have to be available with the product In case of deficiencies or failures please contact the manufact...

Страница 7: ...shall be higher than the outlet pressure Ensure that there are no diameter narrowing and expansion over short distances at the inlet and outlet of the line on which the product will be mounted Before...

Страница 8: ...s use a gland or ball valves at the product inlet and outlet Connect the product to the line without causing mechanical stress It should be remembered that excessive loads to be applied to the body ma...

Страница 9: ...roduct is not reverse mounted After the product is assembled carry out the necessary checks Ensure that the product impermeability is provided example external impermeability visual control Gas Inlet...

Страница 10: ...leased gas is mixed in the atmosphere if the product is equipped with a discharge system and check that outlet and gas impermeability is achieved by appropriate methods foam detector etc 7 Wait until...

Страница 11: ...anizations should be contacted immediately If the product is closed for various reasons during operation the inlet and outlet valve should be closed the problem should be detected and the product shal...

Страница 12: ...struction 8 Monitor the output pressure from the manometer and bring it to the set value and make sure that the slam shut remains installed at the desired value OUTER LEAKAGE TEST 1 Set the inlet pres...

Страница 13: ...ssure increase is achieved in clockwise rotations and pressure decrease in reverse rotations 6 If there is an SSD an increase in safety pressures should be ensured when adjusted output pressures are i...

Страница 14: ...been exceeded All aforementioned tests should be repeated and it shall be ensured that the results are in conformity It is recommended to seal the adjustment devices so that the settings are not chan...

Страница 15: ...n 2 Cleaning and protection of the pipeline before the product in general after commissioning maintenance may be required very often since the pipeline is not clean enough 3 The level of reliability r...

Страница 16: ...spring supplied from the manufacturer properly and without forcing 4 Place the H1 TEMPER NUT No 9 with the appropriate hexagonal wrench to its initial position 5 Manually assemble the SR UPPER COVER P...

Страница 17: ...duct In all cases make sure that nobody is present indoors in any situation which leads to gas release from the product or the line to the atmosphere that no hazardous atmosphere is and or will be for...

Страница 18: ...nsions are in mm Figure 9 Regulation Discharge No 1 G1 4 ISO 228 SSD Discharge No 2 G1 8 ISO 228 SSD Sensing Line No 3 GE12 1 4 For Pipes 12 X 1 5 Regulation Sensing Line No 4 GE12 1 4 For Pipes 12 X...

Страница 19: ...Page 19 of 32 Figure 11...

Страница 20: ...Page 20 of 32...

Страница 21: ...5 C 1013 mbar Q n m h natural gas x K Q n m h x gas Example Q n m h natural gas x 0 78 Q n m h air Correction factor K at 15 C Butane 0 55 Propane 0 64 Oxygen 0 76 Air 0 78 Nitrogen 0 81 Biogas 0 85 C...

Страница 22: ...ight to make changes in the spring settings Please contact the spring manufacturer Internal Sensing Active Internal and External Sensing Active Pd Outlet Pressure bar Maximum Capacities m3 h Natural G...

Страница 23: ...not lift during transportation In case of repacking no humidity or wetness shall remain in the product The product shall be stored in environments which are isolated from forces such as falling tippin...

Страница 24: ...g to the type of problem if you do not prefer to carry out these procedures or if you have despite the performance of such procedures not solved the problem or have not remedied the suspicion of a pro...

Страница 25: ...odel The dimensions of the gas line may be incorrect Increase the nominal width of the pipeline The gas filter before the regulator may be contaminated Carry out maintenance on the gas filter replace...

Страница 26: ...ealed do not perform this process The product line connection may not be fully connected If there is a leak in the outlet connection nozzle remove the product from the line remove the outlet seal manu...

Страница 27: ...s which may cause combustion cigarettes lighters matches etc extinguish all open fires and smoky substances sources that may create sparks and fires do not re start Do not touch turn on or off any ele...

Страница 28: ...rihi 01 11 2020 The name of the Notified Body and No Onaylanm Kurulu un Ad ve Numaras T V NORD System GmbH Co KG 0045 EU Conformity Assessment Method AB Uygunluk De erlendirme Y ntemi 2014 68 EU PED C...

Страница 29: ...name of the Notified Body and No Onaylanm Kurulu un Ad ve Numaras T V NORD System GmbH Co KG 0045 EU Conformity Assessment Method AB Uygunluk De erlendirme Y ntemi 2014 68 EU PED Category I Modul A2 M...

Страница 30: ...gineering Practice SEP Declaration Deklarasyon We declare that our products with a serial number as defined above meet the requirements 2014 68 EU PED Pressure Equipment Directive Article 4 item 3 The...

Страница 31: ...4 84 E mail info eskavalve com Authorized Signature Authorized Stamp THE SELLER S Title Address Phone Fax E mail Authorized Signature Authorized Stamp COMMODITYS S Type Gas Pressure Regulator Brand ES...

Страница 32: ...ing free repairs and in cases where the goods have failed again within the warranty period the maximum period for repair has been exceeded it has been identified by the authorized service station sell...

Отзывы: