External equipments 

(not supplied by EsiWelma) 

 
12VDC   5…8Ah battery 
12VDC 300mA max for piezoelectric buzzer 

 

 

Sensors UR.13. 

 

Power supply 

From UCE13.5 

Sensing element 

Tin dioxide semiconductor 

Housing 

Self extinguising ABS 

Protection degree 

IP44 

Ambient condition 
              temperature 

 
0…+50°C (Operation) - 20…+70°C (Trasport) 

              humidity 

30…90% R.H.. without condensation 

Intervention thresholds 

URG13/A= 10000ppm of methane (20% LEL) 
URG13.P/A= 3700ppm of LPG (20% LEL) 
URO13/A= 200ppm of CO 

 

(*) LEL = Lower Explosivity Limit  

Expected lifetime (average) 

5 years from installation date 

 

 

Expander EXT6.5 

 

Power supply 

10/-15% 

Frequency 

50/60 Hz 

Power consumption 

30VA 

Optional card 

UZY-13CB 

Optical signalling 

Green LED (power on) 
Red LED (failure) 
Red LEDs (3) sensor fail or in alarm condition 

Connection lenght with UCE13.5 

max 80m (1.5mm

 min) 

Other data as for UCE13.5 

 

Sensors UR.13. connectable 

max  6 

 

 

Relay card UZY20-R 

 

Operating 

Positive logic (normally switch on). 
In case of gas alarm contact switches off. 

Contact rating 

Potentially free change over contact 
5(3)A 250VAC 

 

 

Battery charger card UZY-13CB 

 

Voltage output 

13,8VDC 

Charge current 

0.5A max 

Battery (not supplied by EsiWelma) 

12VDC   5…8Ah 

Back up charge with current limiter 

 

 

 

 Conformity 

 

Regulations 
 

Low Voltage 

 

Electromagnetic Compatibility 

 
2014/35/UE 
2014/30/UE 

Standards 

EN50194 

 

EN50270 

 

Содержание Sensigas UR 13/A Series

Страница 1: ...carbon monoxide with tin dioxide semiconductor sensing element ______________________________________________________________________________________________ The UCE13 5 Central Unit with one or more...

Страница 2: ...al UZY20 R relay card and external buzzer if present When the cause of alarm has been removed is necessary to push the reset button on the front cover to return to normal operation After reset red LED...

Страница 3: ..._______________________________________________________________ UCE13 5 EXT6 5 Installation has to be made respecting the temperature and humidity conditions indicated in Technical Data and in an acce...

Страница 4: ...use _______________________________________________________________________________________________ UCE13 5 UCE13 5 housing has standard DIN dimension 144 x 144 mm used for wall mounting or front pan...

Страница 5: ...mpliance with all the laws in force Caution There is no protection against accidental connection with 230VAC on the wrong terminals ____________________________________________________________________...

Страница 6: ...osivity Limit Expected lifetime average 5 years from installation date Expander EXT6 5 Power supply 230VAC 10 15 Frequency 50 60 Hz Power consumption 30VA Optional card UZY 13CB Optical signalling Gre...

Страница 7: ..._________________________________________________________________________________ Diagram 1 Central unit UCE13 5 with 1 3 UR 13 A sensors with 12VDC external buzzer and 12VDC solenoid valve __________...

Страница 8: ...d of the product life or in the event of its replacement For disposal this product is defined as waste from electrical and electronic equipment electronic waste do not dispose of it as household waste...

Отзывы: