background image

 

 

 

 
 

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

11208 V2.0 R1.0  Manual 

Page 5 of 7 

Art. No. 11208 

10 

Software / Control 

The Analog Output 0-10VDC works with a 1-Wire interface of type DS2408 (8-fold I/O device), which is controlled 
with the 1-Wire commands typical for this device.  
The DS2408 device can display a total of max. 256 states through its 8 outputs, which can be read in internally by 
a microcontroller and converted into an analog output signal. 
 
The individual DS2408 outputs have the following values: channel 0 = 1, channel 1 = 2, channel 2 = 4, channel 3 
= 8, channel 4 = 16, channel 5 = 32, etc. The outputs are read by a microcontroller and output as analog values.  
All 8 outputs to value 0 mean 10V output voltage. All 8 outputs to value 1 (or 255 decimal) mean 0V output 
voltage.   
This logic is inverted. The active outputs are added according to their value and output as analog values. Details 
can be found in our example program in the download area of the shop. 

 

Note:

  

The Analog Output 0-10VDC module starts after switching on the supply voltage into the standby mode, in which 
no voltage (0V) is output. In standby mode the DATA LED flashes.  
The module changes to normal operation after a voltage value of less than 10V has been output once. In normal 
operation a voltage between 0-10V can be output. 

 

11 

Control by 1-Wire Controller / 1-Wire Gateway 

The 1-Wire interface of the Analog Output 0-10VDC is controlled by standard commands for the device DS2408. 
The Analog Output 0-10VDC can easily be controlled via a 1-Wire Controller / 1-Wire Gateway. The following 
command is available for this purpose. 
 

11.1 

Set analog output 

Use the following command to set a new analog value. 

 

Command 
SET,OWD,OUTA,OWD-number, output voltage

  

Example: SET,OWD,OUTA,1,1000  

=> OWD1,10,00V 

 

11.2 

Data output 1-Wire controller / 1-Wire gateway 

For the 1-Wire Analog Output module 0-10V, the following data are output for the status of the analog value.  
The following formatting is available since firmware 1.18_43. 

data output

  

1_OWD1|1000   

=> Controller No._device No._data record | analog value, example 1000 = 10,00V 

 
Further information in regards to options and commands can be found in the current 1-Wire Controller /1-Wire 
Gateway documentation. 

 

12 

Operating conditions 

The device may only be operated at the specified voltages and ambient conditions. The device may only be 
used in dry indoor areas. 
If condensation forms inside the unit, allow at least 2 hours for the unit to acclimatize. Do not operate the 
module in an environment in which flammable gases, vapors or dusts are present or could be present. The 
building group can be operated only under the supervision of an electrically skilled person. 
In industrial facilities, the accident prevention regulations of the federation of industrial professional 
associations for electrical installations and equipment must be observed. 
 
 

13 

Assembly 

The location of the assembly must be protected against humidity. The device may be used only in dry inside 
spaces. The device is designed to be assembled as a fixed device within a switchboard. 
.  
 

Содержание 11208

Страница 1: ...e safety notes 2 Product description With the Analog Output a DC voltage in the range of 0 10V with a resolution of 8 bits can be easily output This DC voltage can be output for control e g of a heating mixer dimmer or other power control units The analog output is galvanically isolated from the 1 wire bus and the power supply The isolation avoids ground loops or effects due to potential differenc...

Страница 2: ...face 1 Wire bus 12V data 5V signal level and GND Ground Operating voltage 12V 10 current consumption max 30mA Current consumption max 20 mA output with 10k load Display 2 x LED green data update and supply voltage Connection screw terminals up to 2 5qmm cable cross section Note A 12V supply voltage is required to operate the module The use of one of our 1 Wire Hub devices is recommended Avoid to c...

Страница 3: ...our web shop as a separate document Module topside analog output 4 negative output 5 analog output Module bottom side 1 Wire Bus 1 GND Ground 2 1 Wire data 5V signal level 3 12V voltage Display Designation Function LED green PWR Display for supply voltage LED green Data Flashing when new data value is received and output data update After switching on the supply voltage the module starts in Start ...

Страница 4: ...ESERA Automation 2020 www esera de 11208 V2 0 R1 0 Manual Page 4 of 7 9 Connection Example Here we would like to show you a connection example of the Analog Output 0 10V in combination with a 1 Wire Controller 20 or 1 Wire Gateway 20 Modbus This connection example is available as a separate document in the ESERA online shop download area of the article Here the example is only shown in reduced siz...

Страница 5: ...er 1 Wire Gateway The 1 Wire interface of the Analog Output 0 10VDC is controlled by standard commands for the device DS2408 The Analog Output 0 10VDC can easily be controlled via a 1 Wire Controller 1 Wire Gateway The following command is available for this purpose 11 1 Set analog output Use the following command to set a new analog value Command SET OWD OUTA OWD number output voltage Example SET...

Страница 6: ...rational and connection errors outside of our control we assume no liability of any kind for any resulting damage Kits should be returned without their housing when not functional with an exact error description and the accompanying instructions Without an error description it is not possible to repair For time consuming assembly or disassembly of cases charges will be invoiced During installation...

Страница 7: ...protected designations of their respective owners and are hereby expressly recognized as such by us The mention of these designations logos names and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of ESERA GmbH on these designations logos names and trademarks Moreover from their appearance on ESERA GmbH webpages it cannot be concluded tha...

Отзывы: