Device Profile Area
CAN-CBX-DIO8
Manual • Doc.-No.: C.3010.21 / Rev. 3.1
Seite 95 von 123
8.10.4 Read Input 8-Bit (6000
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
6000
h
0
no_of_entries
1
1
unsigned 8
ro
1
read_input_DI8-DI1
0...FF
h
-
unsigned 8
ro
Assignment of the variables read_input_DI8-DI1:
Index: 6000
h
, Sub-index: 1
Bit:
7
6
5
4
3
2
1
0
Input:
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
An input bit is read as ‘1’, if the corresponding input is active, i.e. voltage is ‘on’ (if the according
bit in object 6002