2.2 STANDARD FEATURES

Code

Description

A2a

Relay Voltage ON (K1)

If the device is supplied, relay K1 is activated and the terminal board contact is closed. In case of power failure, this

 

contact is open.

B10b

Manual activation of every single output from keyboard

By keyboard, it is possible to activate manually and individually every single output for an operation test.
Press key C to select the desired output to be activated. Press key A to activate the output.
The output is holded active for all the time that key A is pressed. It allows to measure the output voltage by using a

 

tester.

In case of anomalous operating, do this test with electrovalves disconnected.

B1b

Select Number of outputs

The selection of the number of outputs to be control led is connected by keyboard in SET MODE. If you set 0 or AUTO

 

in this function the sequencer will automatically select the connected loads by skipping the non connected ones.

 

Minimum load 5W ÷ 12 W depending on the output voltage. If the load is below of the minimum,  the autoselection does

 

not work correctly, set the number of outputs in set up.

B2x

Activation time from 0.05 to 5.00 sec.

B3x

Interval time from 1 to 999 sec.

If the pulse time is lower than 1 sec. it is possible to set any interval time value in the range indicated.
If the activation time is higher than 1 sec. the minimum settable interval time is:
Minumum interval time = 5 times pulse time (B2x)

B8a

Short-circuit protection of every single output

In case of short circuit, the output is automatically skipped, the relay K1, normally active, is deactivated and the terminal

 

board contact opens.

The display alternatively shows code E1 and the number of the faulty output.
Press key B to reset the alarm.

B9b

Electric control of output activation

If a solenoid valve is not activated, the relay K2  indicate the alarm condition and the display shows the alarm condition

 

code E2 (See alarm description).

Press key 'E' to reset alarm condition.
ATTENTION: this function will be active only if the automatic selection of the load in set up is not selected.
The alarm switch on after 5 consecutive fails on the same output.

C0

Input activation from external contacts

In Set up you can activate or deactivate the control of all the inputs of the device.
If inputs are deactivated, they are considered as always closed and no jumper is required on the terminal board.
Use a jumper for unused inputs if you activate them.
NOTE: all inputs of the device have to be connected to external contact without voltage.

C4c

Cleaning cycle

If all the conditions necessary for the start of cleaning cycle (e.g. fan On, external consents C6 or D6 present) are

 

present  when supply voltage is switched on, automatically the device activates the outputs in sequencial way with

 

timing set by keyboard

C6a

ON/OFF cleaning cycle from external pressure switch. STOP at the end of the cycle

With digital inputs enabled and with contact C6a open the cleaning cycle stops at the end of the cleaning cycle and

 

display shows 'CYCLE STOPS FOR LOW dP'.

When C6a is closed the cleaning cycle restart.
NOTE. Put a wire between the clamps of input C6a if not used with inputs enabled.

D14a

Operation hours-counter

In Setup it is possible to visualize an hours counter. This counter is active when the cleaning cycle in On. In case of fan

 

stop, consent D6 not present or with the device in Setup the counter stops.

D1a3

Additional cycles from voltfree contact. ALWAYS enabled.

By connecting an NO auxiliary contact of the circuit intended to drive the fan with the sequencer, it is possible to add a

 

pre-set number of cleaning cycles after the fan stop. Their number can be set from 0 to 99 by keyboard.

Post-cleaning cycles are activated even if dP = 0 or C6x open.
If contact D1a3 is open, the display shows the indication of fan stop (See operation table 6.1).
The display shows 'POST-CLEANING ACT' or decimal points blink, according to the model, during additional cycles.
NOTE. Jump D1a3 clamps if it is not used with inputs enabled.

Содержание Ex22DSR

Страница 1: ...ual activation of every single output from keyboard B1b Select Number of outputs B2x Activation time from 0 05 to 5 00 sec B3x Interval time from 1 to 999 sec B8a Short circuit protection of every single output B9b Electric control of output activation C0 Input activation from external contacts C4c Cleaning cycle C6a ON OFF cleaning cycle from external pressure switch STOP at the end of the cycle ...

Страница 2: ... alarm description Press key E to reset alarm condition ATTENTION this function will be active only if the automatic selection of the load in set up is not selected The alarm switch on after 5 consecutive fails on the same output C0 Input activation from external contacts In Set up you can activate or deactivate the control of all the inputs of the device If inputs are deactivated they are conside...

Страница 3: ...s from external contact active See Setup 5 1 G1 Maximum load power 25W per output HVA Input voltage selection By some jumpers on the board it is possible to change the supply voltage See label on the device pr board layout The ouput voltage for the electrovalves BUS line is fixed 24VDC JP1 Supply voltage selection between 115VAC or 230VAC SL Multi language display In Set up it is possible to selec...

Страница 4: ... the device and remove it if it is present by using wet cloth 3 9 For supply voltages cabling and voltages applicable to the relay contacts follow the current rules 3 10 For all input control signals to the Timer D1a D5 D6 use anti flame wires with a minimum section of 0 5 mm 3 11 For the electrical connection of the supply voltage and filter cleaning electrovalves use anti flame wires with a mini...

Страница 5: ...1 to 999 sec 001 999 B3x 5 sec 05 POSTCL INT B3c 005 sec Interval time between ev during post cleaning from 1 to 999 sec 001 999 B3c 5 sec 06 POST CYCLES D1x 002 cycles Number additional cycles after fan stop 00 99 D1x 5 07 ELECTROVAL N B1b 016 ev Selection Number of electrovalves B1a 08 EV TEST B10b 001 OFF TEST Manual activation of every single ev from keyboard B10 09 HOURS COUNTER D14a 00000 Ho...

Страница 6: ...TILATOR STOP Cycle stops waiting for fan start or dP under set fan threshold See SET 11 section 5 1 D1x ACTIVAT EV 003 Activation output solenoid valve 3 WAITING 005 sec Waiting time before activation of the next ev CYCLE STOP FOR dP LOW Cycle stopped due to lack consensus C6A Contact C6a D6a open See 2 2 C6a POSTCLEANING ACT Additional cycles after fan stop active D1x Keypad lock Option on reques...

Страница 7: ...D ELECTROVALVE 003 Overload alarm solenoid valves 3 B8b E2 ACT FAILED ELECTROVALVE 003 Solenoid valve not activated Solenoid valves 03 option on request B9x B6x 8 1 INFORMATION AND GUIDE ON THE DISPLAY 8 1 INFORMATION AND GUIDE ON THE DISPLAY Not available for this model ...

Страница 8: ...9 1 WIRING DIAGRAM ...

Страница 9: ...10 1 ELECTRONIC BOARD SIZE AND VOLTAGE SETTINGS ...

Страница 10: ...11 1 ENCLOSURE DIMENSIONS ...

Страница 11: ...he microprocessor could be modified by external factor Switch Off the supply voltage of the sequencer Hold down key A and switch on the supply voltage By means of this operation the default data are loaded in set up Adjust the zero dP reading and the other parameters according to the filter s needs 13 1 WARRANTY The warranty lasts 4 years The company will replace any defective electronic component...

Страница 12: ...escribed above is in conformity with the relevant Union harmonisation legislation The object of the declaration described above is in conformity with the relevant Union harmonisation legislation Directives 2014 30 UE 2014 34 UE and 2011 65 UE Directives 2014 30 UE 2014 34 UE and 2011 65 UE The following harmonised standards and technical specifications have been applied The following harmonised st...

Страница 13: ... by the final user The company does not assume any responsibility Use only cable glands IP65 ATEX certified with same or superior certification of the device and type ISO R 68 The fixing holes must be done with the right diameter indicated for that cable gland With the purpose to avoid the entry of dust inside the equipment through the pneumatic connections for the reading of the dP insert on such...

Отзывы: