18.5.8 P3
When current is over the specific value (Single phase unit 5/7kW 18A, single phase unit 10/12kW 30A, three
phase unit 15A), the system will display P3 protection, the ODU in standby.
When the current goes back to normal range, P3 disappears and normal operation resumes.
P3: Over current protection
Check whether the input current is large
than the specific value
Check whether the ambient
temperature is too high
Yes
Low heat exchange efficiency, causes may include
dirty heat exchanger, dirty plate type heat
exchanger, abnormal fan operation, water pump
error, too closed outdoors installation, etc.
No
Inspect the system and
fix the error
The refrigerant pipe is block, caused by
crushed or bent pipe, blocked EXV valve,
blocked filter, etc.
PCB is damaged
PCB is damaged, replace PCB
No
Yes
Stop the unit and wait for
ambient temperature get down
Yes
No
Replace PCB
Inspect the system and fix
the error
Yes
No
83
V.2
Содержание EMCH-10W/1
Страница 14: ...14 6 Dimensiones EMCH 07W 1 Unidad mm EMCH 10W 1 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 Unidad mm V 2...
Страница 16: ...16 6 Diagrama de cables EMCH 07W 1 V 2...
Страница 17: ...17 EMCH 10W 1 V 2...
Страница 18: ...18 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Страница 29: ...29 V 2...
Страница 30: ...30 V 2...
Страница 31: ...31 V 2...
Страница 33: ...33 12 Vista ampliada EMCH 07W 1 28 1 28 2 28 3 28 5 28 6 28 4 28 7 V 2...
Страница 35: ...35 EMCH 10W 1 V 2...
Страница 37: ...37 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Страница 53: ...53 Para acceder el panel de control abrir la tapa retirar el tornillo 1 y tornillo 2 subir el panel 3 V 2...
Страница 95: ...MINI CHILLER INVERTER INSTALLATION S AND USER S MANUAL EMCH 10W 1 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Страница 110: ...7 Wiring Diagram EMCH 07W 1 15 V 2...
Страница 111: ...EMCH 10W 1 EMCH 12W 1 16 V 2...
Страница 112: ...EMCH 14W 3 EMCH 16W 3 17 V 2...
Страница 121: ...11 Hydraulic Data 11 1 Useful pump head curves P C constant curve for 7 kW P C constant curve for 10 12 14 16 kW 26 V 2...
Страница 122: ...11 2 Water Side Water Pressure Drop EMCH 07W 1 EMCH 10W 1 Heat exchanger pressure drop water side 27 V 2...
Страница 123: ...EMCH 12W 1 EMCH 14W 3 28 V 2...
Страница 124: ...EMCH 16W 3 29 V 2...
Страница 126: ...13 Exploded View EMCH 07W 1 31 V 2...
Страница 128: ...EMCH 10W 1 EMCH 12W 1 33 V 2...
Страница 130: ...EMCH 14W 3 EMCH 16W 3 35 V 2...