15
ST1
FT1
P1 P2 P3
ST2
FT2
P4 P5 P6
STOP
P7 P8
P11 P12
LOCK
FCA1
FCC1
P15 P14 P16
P22 P23
Courtesy
Light
Lamp.
G7 G8
G9 G10
24Vac
G4
G5
G6
G1
G2
G3
FCA2 COM FCC2
SCA
VIVO-M201: 230Vac/50Hz
VIVO-M201M: 125Vac/60Hz
N
L
POWER
MOTOR2 (G2-G1-COM)
MOTOR1 (G2-G1-COM)
G4 G5 G6
G1 G2 G3
P195V
A1, A2
operators
C1, C2
capacitors:
CA43 and CA53 (230V): 8μF
CA43M and CA53M (125V): 25μF
DL4
gate opening
DL5:
gate closing
PUL1
close
mini-pushbutton
PUL2
open
mini-pushbutton
T
Earth connection
Operator connections A1 / A2:
G1 / G4
open,
CA43 and CA53 (230V): brown wire
CA43M and CA53M (125V): red wire
G2 / G5
close, black wire
G3 / G6
common (COM),
CA43 and CA53 (230V): grey wire
CA43M and CA53M (125V): white wire
T
earth (GND),
CA43 and CA53 (230V): yellow - green wire
CA43M and CA53M (125V): green wire
When pressing PUL1, DL5 lights up and
the G2/G5 and G3/G6 cable
connectors are activated.
When pressing PUL2, DL4 lights up and
the G1/G4 and G3/G6 cable
connectors are activated.
Electrical connections
For
CA43 and CA53 (230V / 50Hz)
operators we recommend using the
VIVO-M101
control panel (for
single operator facilities) and the
VIVO-M201
control panel (for dual operator facilities).
For
CA43M and CA53M (125V / 60Hz)
operators we recommend using the
VIVO-M101M
control
panel (for single operator facilities) and the
VIVO-M201M
control panel (for dual operator facilities).