19
GB
OPERATIVE MODE
DISPLAY FUNCTIONS
The upper display shows the measured value
while the lower display shows the programmed set
point value (we define the above condition as
“normal display mode”).
Note: When the rate of change (
Grd1
,
Grd2
) is
utilized, the displayed set point value may be
different from the operating setpoint (see P48).
By pushing the FUNC key for more than 3 s but
less than 10 s. it is possible to change the
information on the lower display as follows:
°C
or
°F
according to the selected input range.
NOTE: this indication will be shown only when a
TC or RTD input is selected.
Push "FUNC" key again, the lower display will
show:
P.
followed by the valve position indication.
Push "FUNC" key again, the lower display will
show:
r.
followed by power value assigned to the output
programmed with "
rEU
" action (from 0 to 100%).
Push "FUNC" key again, the lower display will
show:
d.
followed by power value assigned to the output
programmed with "
dir
" action (from 0 to 100%).
Push FUNC key again, the lower display will
show:
U.
followed by the firmware version.
Push FUNC pushbutton again. The display will
return in "Normal Display Mode".
NOTE: These informations will be displayed only if
relative function has been previously configured.
When no pushbutton is pressed during the time
out (see P46), the display will automatically return
in "Normal Display Mode".
In order to keep the desired information
continuously on the lower display, depress "
s
" or
"
t
" push- buttons to remove the timeout.
When is desired to return in "Normal Display
Mode" push FUNC push-button again.
INDICATORS
s
Lit when the OUT 1 (
s
) relay contact is
closed (the instrument is opening the
valve) or this output is used as time
proportioning control output and it is in ON
condition.
t
Lit when the OUT 2 (
t
) relay contact is
closed (the instrument is closing the valve).
MAN
Lit when the instrument is in MANUAL
mode.
OUT3 Lit when the alarm 1 is in the alarm state or
this output is used as time proportioning
control output and it is in ON condition.
OUT4 Lit when the alarm 2 is in alarm condition.
Flashing with slow rate when the alarm 3 is
in alarm condition.
Flashing with high rate when the alarm 2
and 3 are in alarm condition.
When the OUT 4 is driven by serial link,
this LED is lit when the output 4 is ON.
SMRT Flashing when the first part of the SMART
algorithm is active.
Lit when the second part of the SMART
algorithm is active.
The decimal point at the right hand of the LSD of
the 2 numerical displayes show the follouing
indication:
REM
Lit when the instrument is in REMOTE
condition (functions and parameters are
controlled via serial link).
SPX
Flashing with slow rate when SP2 is used.
Flashing with high rate when a temporary
set point from serial link is used.
LFS-servo-1-02.p65
1/14/02, 3:44 PM
19