Power 

Þ

 nominal current conversion

In order to have a quick check of the device
working conditions, we provide you the formulas
to calculate the nominal current for each device in
relation to the total power and the connection
type.
Preliminary notes:
1)

Only a resistive load must be applied to the
device, so in the following formulas the cos 

f

will be considered equal to 1.

2)

the formulas related with the 3-phase
applications are referred to a balanced
3-phase system only.

Single-phase connection

I

P

V

RMS

RMS

=

where:
P   = power (in Watts).
V

RMS

 = phase to neutral or phase to phase

voltage (in Volts)

I

RMS

 = nominal current (in Amperes)

3 -phase without neutral connection (star or

delta  application)

I

P

V

RMS

RMS

=

·

3

where:
P   = Total load power (in Watts).
V

RMS

 = phase to phase voltage (in Volts)

I

RMS

 = nominal current (in Amperes)

3-phase with neutral connection (star

application)

I

P

V

RMS

RMS

=

·

3

where:
P   = Total load power (in Watts).
V

RMS

 = phase to neutral voltage (in Volts)

I

RMS

 = nominal current (in Amperes)

ESR-AC10A.p65

2/8/02, 2:21 PM

8

  2 rue René Laennec 51500 Taissy France

 

Fax: 03 26 85 19 08,  Tel : 03 26 82 49 29

 

E-mail:[email protected]
Site web : www.hvssystem.com

 

 

 

 

 

 

 

 

 

 

 

Содержание ESR-AC

Страница 1: ...170 IU0 IXR A00 11 99 A r USER MANUAL r ISTRUZIONI D USO ESR AC00A p65 2 8 02 2 20 PM 1 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssystem hvssystem com Site...

Страница 2: ...out A 1 GB INDICE MONTAGGIO 1 AVVERTENZE 1 Norme generali per il fissaggio 1 Fissaggio a parete 3 Fissaggio tramite barra OMEGA 4 COLLEGAMENTI ELETTRICI 5 NOTE GENERALI PER IL COLLEGAMENTO 5 AVVERTEN...

Страница 3: ...ESR AC00A p65 2 8 02 2 20 PM 3 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssystem hvssystem com Site web www hvssystem com...

Страница 4: ...roximity to the equipment and within easy reach of the operator it shall be marked as the disconnecting device for the equipment NOTE a single switch or circuit breaker can drive more than one device...

Страница 5: ...out to the bottom and 150 mm out to the top of the cabinet or any other element I E raceway which can compromise the air flow Fig 3 ESR AC10A p65 2 8 02 2 21 PM 2 2 rue Ren Laennec 51500 Taissy France...

Страница 6: ...WALL MOUNTING For wall mounting you can use the A holes In this case it is advisable to use M4 screws with a torque of 1Nm For the mounting template and the mechanical dimensions of all models please...

Страница 7: ...s MOUNTING Fig 5 REMOVING Fig 6 For the mechanical dimensions of all models please refer to the appropriate drawing located in the Appendix A screwdriver Omega DIN rail ESR AC10A p65 2 8 02 2 21 PM 4...

Страница 8: ...er wires only 6 The neutral if used must be connected to the 2 and 4 terminals 7 The power input IS NOT fuse protected so it is necessary placing an external one selected among the types shown in Tabl...

Страница 9: ...67 F mini mumtemperaturerating Thefollowingtableshows the recommended sizes Nominal f wires AWG current mm2 12 A 2 5 14 18 A 4 12 25 A 6 10 40 A 10 8 60 A 16 6 80 A 25 4 without wire terminal 10 The t...

Страница 10: ...max 2 Nm advisable 1 5 Nm for the terminals A1 and A2 is max 0 5 Nm advisable 0 33 Nm Fig 7 B ETR TERMINAL BLOCK ESR AC10A p65 2 8 02 2 21 PM 7 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 0...

Страница 11: ...only Single phase connection I P V RMS RMS where P power in Watts VRMS phase to neutral or phase to phase voltage in Volts IRMS nominal current in Amperes 3 phase without neutral connection star or de...

Страница 12: ...ESR ESR T P L1 N L2 EARTH POWER LINE Signal Load Fuse 100 to 240 VAC or 24 V AC ESR AC10A p65 2 8 02 2 21 PM 9 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssy...

Страница 13: ...2 T L3 Power Line EARTH Fuse Fuse Y or star connection without neutral Delta connection 100 to 240 VAC or 24 V AC ESR AC10A p65 2 8 02 2 21 PM 10 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19...

Страница 14: ...line Earth R L1 S L2 T L3 Signal generator Y or star connection without neutral Delta connection ESR AC10A p65 2 8 02 2 21 PM 11 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 4...

Страница 15: ...L1 T L3 S L2 N EARTH POWER LINE Fuse Fuse Fuse Y or star connection with neutral 100 to 240 VAC or 24 V AC ESR AC10A p65 2 8 02 2 21 PM 12 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel...

Страница 16: ...T L3 S L2 N EARTH POWER LINE Fuse Fuse Fuse 100 to 240 VAC or 24 V AC ESR AC10A p65 2 8 02 2 21 PM 13 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssystem hvssy...

Страница 17: ...minute between command and power circuits 3500 V DC Operational temperature from 0 to 50 C from 32 to 122 F Humidity from 20 to 85 RH non condensing Storage temperature from 20 to 70 C 4 to 158 F CE M...

Страница 18: ...eak voltage DV Dt PRV Total power dissipation I Inom Weight Amp V 12 240 240 V 12 A 160 A 128 900 V 250 V ms 800 V 22 W 510 g Amp V 18 240 240 V 18 A 208 A 259 900 V 250 V ms 800 V 32 W 510 g ESR AC10...

Страница 19: ...0 1300 V 1000 V ms 1200 V 112 W 2000 g MODEL CHARACTERISTICS Nominal voltage Nominal current 50 C Non rep surge current I2 t for fusing 10 ms Non rep peak voltage DV Dt PRV Total power dissipation I I...

Страница 20: ...1300 V 1000 V ms 1200 V 168 W 1950 g MODEL CHARACTERISTICS Nominal voltage Nominal current 50 C Non rep surge current I2 t for fusing 10 ms Non rep peak voltage DV Dt PRV Total power dissipation I Ino...

Страница 21: ...peration on the device you have to be sure that its temperature is decreased to an acceptable value MAINTENANCE 1 REMOVE POWER FROM THE DEVICE BY USING A MECHANICAL CIRCUIT BREAKER 2 Using a vacuum cl...

Страница 22: ...tura e la linea essodevetrovarsiinstrettavicinanzadell appa recchio ed essere facilmente raggiungibile da partedell operatore Deve essere marcato come il dispositivo di interruzionedell apparecchio NO...

Страница 23: ...no installati Le stesse distanze vanno rispettate nei confronti di eventuali canaline o altri elementi che possano limitare la ventilazione dello apparecchio Fig 3 ESR AC40A p65 2 8 02 2 24 PM 2 2 rue...

Страница 24: ...o a parete utilizzare fori A In questo caso si consiglia l utilizzo di viti M4 serrate con una coppia minima di 1 Nm Per le dime di foratura e le dimensioni di ingombro fare riferimento allo specifico...

Страница 25: ...ig 5 RIMOZIONE Fig 6 Per le dimensioni di ingombro fare riferimento allo specifico disegno meccanico I disegni meccanici di tutti i modelli sono riportati nell Appendix A Cacciavite Barra Omega DIN ES...

Страница 26: ...rame 6 Se prevista la connessione al neutro collegarlo al terminali 2 e 4 7 L ingresso di potenza NON protetto da fusibile quindi necessario prevederne uno esterno scelto tra quelli indicati nella Tab...

Страница 27: ...18 A 4 12 25 A 6 10 40 A 10 8 60 A 16 6 80 A 25 4 senza capocorda 10 La coppia di serraggio per i morsetti 1 2 e morsetto di terra degli apparecchi ESR T e ESR deve essere pari a per tutti i modelli...

Страница 28: ...igliata 1 5 Nm Per il serraggio dei morsetti A1 e A2 la massima coppia di serraggio pari a 0 5 Nm mentre la coppia consigliata pari a 0 33 Nm Fig 7 BMORSETTIERADEGLIAPPARECCHIETR ESR AC40A p65 2 8 02...

Страница 29: ...ollegamento monofase I P V eff eff dove P potenza espressa in Watt Veff tensione fase neutro o fase fase espressa in Volt Ieff corrente nominale espressa in Ampere Collegamento a stella o triangolo tr...

Страница 30: ...comando Fuse da 100 a 240 V c a oppure 24 V c a COLLEGAMENTI Collegamento monofase ESR AC40A p65 2 8 02 2 24 PM 9 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hv...

Страница 31: ...bile Collegamento a stella senza neutro Collegamento a triangolo CARICO da 100 a 240 V c a o 24 V c a Signal generator ESR AC40A p65 2 8 02 2 24 PM 10 2 rue Ren Laennec 51500 Taissy France Fax 03 26 8...

Страница 32: ...utro Collegamento a triangolo CARICO LINEA da 100 a 240 V c a o 24 V c a Fusibile Fusibile Signal generator ESR AC40A p65 2 8 02 2 24 PM 11 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel...

Страница 33: ...ibile Fusibile Fusibile Collegamento a stella con neutro CARICO R L1 S L2 T L3 da 100 a 240 V c a oppure 24 V AC ESR AC40A p65 2 8 02 2 24 PM 12 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 0...

Страница 34: ...AC N TERRA LINEA Fusibile Fusibile Fusibile Collegamento a stella aperta CARICO R L1 S L2 T L3 ESR AC40A p65 2 8 02 2 24 PM 13 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49...

Страница 35: ...A Isolamento tra circuiti di potenza e massa 2200 V c c per 1 minuto tra circuiti di comando e potenza 3500 V c c Temperatura di funzionamento da 0 a 50 C Umidit da 20 ad 85 di RH non condensante Temp...

Страница 36: ...di picco non ripetitiva DV Dt PRV Potenza totale dissipata I Inom Peso Amp V 12 240 240 V 12 A 160 A 128 900 V 250 V ms 800 V 22 W 510 g Amp V 18 240 240 V 18 A 208 A 259 900 V 250 V ms 800 V 32 W 51...

Страница 37: ...1300 V 1000 V ms 1200 V 112 W 2000 g MODELLO CARATTERISTICHE Tensione nominale Corrente nominale 50 C Corrente di picco non ripetitiva I2 t per fusibile 10 ms Tensione di picco non ripetitiva DV Dt PR...

Страница 38: ...1300 V 1000 V ms 1200 V 168 W 1950 g MODELLO CARATTERISTICHE Tensione nominale Corrente nominale 50 C Corrente di picco non ripetitiva I2 t per fusibile 10 ms Tensione di picco non ripetitiva DV Dt PR...

Страница 39: ...asi operazione sull ap parecchio assicurarsi che la temperatura del dissipatore sia scesa a livelli accettabili MANUTENZIONE ORDINARIA 1 TOGLIERE TENSIONE ALL APPARECCHIO tramite il disgiuntore meccan...

Страница 40: ...SUNGEN DIMENSIONI E FORATURE Fig Abb A 1 APPENDIX A Dimensions are in mm inches ESR T 12 ESR T 18 EXR A 02 p65 2 8 02 3 04 PM 1 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49...

Страница 41: ...A 2 Dimensions are in mm inches ESR 25 ESR 40 EXR A 02 p65 2 8 02 3 04 PM 2 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssystem hvssystem com Site web www hvs...

Страница 42: ...A 3 Dimensions are in mm inches ESR 60 ESR 80 EXR A 02 p65 2 8 02 3 04 PM 3 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssystem hvssystem com Site web www hvs...

Страница 43: ...are in mm inches ETR 25 A ETR 40 60 A Fig Abb A 4 EXR A 02 p65 2 8 02 3 04 PM 4 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 E mail hvssystem hvssystem com Site web www...

Страница 44: ...0321481111 Fax 39 0321481112 E maileroelectronic ero eurotherm co uk Http www eroelectronic com ESR ACz0A p65 2 8 02 2 26 PM 1 2 rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49...

Отзывы: