7
GB
11)The torque for tightening the terminals 1, 3, 5, 7
and earth of the ETR is:
max = 2 Nm
advisable = 1.5 Nm
- for the terminals A1 and A2 is:
max = 0.5 Nm
advisable = 0.33 Nm
Fig. 7/B
ETR TERMINAL BLOCK
ESR-AC10A.p65
2/8/02, 2:21 PM