![ERL MIT161 Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/erl/mit161/mit161_application-and-commissioning-manual_2423789017.webp)
17
changes reset time delay by 1 sec for each pressing. After selecting the desired setting,
once again press the
→
key (Sub menu LED goes OFF) to get back the main menu.
The recommended setting is 0sec.
6.4. Acceptance of Settings (ENTER)
For the relay to accept the above setting changes press
X
key once, now the display goes
off and the settings are updated. By pressing any key again
Indication will appear
Ensure all the chosen settings. In case of any changes required use Sub menu key and then
do the changes and finally press enter
X
key once.
ENSURE TO PRESS ‘ X ’ KEY TO ACCEPT THE CHANGES
7. TO CHECK THE RELAY VERSION
Press
×
key four times, example of relay version display is as follows:
-
Represent MIT 161 relay version 1
To get back the main menu, press
↑
or
↓
key.
8. TO CANCEL SETTING WHILE CHANGING (CANCEL)
While the particular setting is being changed (using
↑
or
↓
key) with Submenu LED ON
by pressing X key, the original setting is restored
9. TRIP INDICATION AND RESETTING OF TRIP INDICATION (RESET)
When the relay operates, RED " TRIP" LED indicates tripping.
By pressing repeatedly the arrow key you will get all trip indication. That is if Earth fault
tripped
will reappear. Where as if both (Earth fault & Low set) are tripped
will appear alternatively for each pressing of the key.
Suppose Earth fault has started but not initiated trip, but Low set is tripped then pressing
any arrow key
(Indicates Earth fault is started)
(Indicates Low set is
operated) will appear alternatively for each pressing of the key.
Once the fault is cleared, press
×
key twice to reset the trip indication.
The trip indication and settings will be retained in Non - volatile memory during auxiliary
DC power supply failure.