D05125R01.20
F-PRO 116 User Manual
1-5
AC Current Inputs
F-PRO is provided with terminal blocks for up to 5 AC current
inputs (3 Phase Current, 1 Neutral and 1 SEF). 1A and 5A are
separate terminals, 1A / 5A CT Secondary is Site Selectable.
To refer the complete schematic circuits; see
“AC Schematic
Drawing”
&
“
DC Schematic
Drawing” in
External Inputs
The F-PRO relay has 4 external inputs with a factory selectable
voltage level. External DC voltages of either 24/30 volts, 48/50
volts, 110/125 volts or 220/250 volts nominal are available
depending on the ordering code.
Relay Inoperative Alarm
Output
If the relay becomes inoperative, then the Relay Inoperative Alarm
output contact closes. Output Contact 6 may be configured as
Relay Inoperative Alarm Contacts. During the relay inoperative
period, all tripping functions are blocked.
Output Relay Contacts
The F-PRO relay has 6 output relay contacts. Each contact is
programmable and has breaker tripping capability. All output
contacts are isolated from each other. All the contacts are
provided with settable dropout timers (0-1 sec) - applicable for
self reset.
If function reset time & the output contact reset time both are set
in the IED; then, the higher value will be taken for relay drop out.
Example:
51 function is chosen with reset DTL delay 0.5 sec and
the output contact dropout time is 0.8 sec, then 0.8 sec will be the
dropout time of the output contact.
1.4 Model Options/Ordering
•
The relay is available in E4 size and flush mount type along with standard for details
see “Mechanical Drawings” in
•
The external inputs are 24/30, 48/50, 110/125 or 220/250 Vdc rated. The Auxiliary
supply is 20-60 Vdc or 80-300 Vdc rated.
•
All of the above options must be specified at the time of ordering.
Содержание F-PRO 116
Страница 2: ......
Страница 12: ...1 2 F PRO 116 User Manual D05125R01 20 Figure 1 1 F PRO 116 Relay Function Line Diagram...
Страница 16: ...1 6 F PRO 116 User Manual D05125R01 20 Figure 1 4 Ordering Template...
Страница 20: ......
Страница 30: ......
Страница 84: ...7 12 F PRO 116 User Manual D05125R01 20 Figure 7 10 Point Map...
Страница 94: ......
Страница 96: ......
Страница 124: ......
Страница 148: ......
Страница 149: ...D05125R01 20 F PRO 116 User Manual Appendix H 1 Appendix H Mechanical Drawings H 1 Front View...
Страница 150: ...Appendix H 2 F PRO 116 User Manual D05125R01 20 H 2 Rear View...
Страница 151: ...D05125R01 20 F PRO 116 User Manual Appendix I 1 Appendix I AC Schematic Drawing...
Страница 152: ......
Страница 153: ...D05125R01 20 F PRO 116 User Manual Appendix J 1 Appendix J DC Schematic Drawing...
Страница 154: ......
Страница 155: ...D05125R01 20 F PRO 116 User Manual Appendix K 1 Appendix K Connection Diagram...
Страница 156: ......