Home > SPR1100 Handbook > Installing the Equipment > Mounting in a Rack > Care in Positioning
Care in Positioning
Positioning the Unit
CAUTION!
The following points must be taken in to consideration when positioning the unit.
The fans contained within this unit are not fitted with a dust/insect filter. Pay attention to
the environment in which it is to be used.
1.
Do not install units so that the air intake of one aligns with the outlet on another. Provide
baffles and adequate spacing.
2.
The equipment should never be placed near or over a radiator or other source of heat. It
should not be placed in a built-in installation such as a rack unless proper ventilation is
provided and the instructions have been adhered to.
Allow at least 40 mm free air-space at each side of the equipment to ensure adequate
cooling.
Racks containing stacked equipment may need to be forced air-cooled to reduce the
ambient temperature within the rack.
Protection from Moisture
Do not install this equipment in areas of high humidity or where there is a danger of water
ingress.
Cooling
Side openings in the unit, as well as side-mounted cooling fans, are provided for ventilation.
They ensure reliable operation of the product and protect it from overheating.
Содержание SPR1100
Страница 22: ......
Страница 23: ...Ethernet Port Numbering Ericsson AB 2011 All rights reserved ...
Страница 26: ......
Страница 27: ...Ethernet Port Numbering Ericsson AB 2011 All rights reserved ...
Страница 30: ......
Страница 31: ...Ethernet Port Numbering Ericsson AB 2011 All rights reserved ...
Страница 34: ......
Страница 35: ...Ethernet Port Numbering Ericsson AB 2011 All rights reserved ...
Страница 74: ... Ericsson AB 2011 All rights reserved ...
Страница 98: ... Ericsson AB 2011 All rights reserved ...
Страница 106: ... Ericsson AB 2011 All rights reserved ...
Страница 109: ... Ericsson AB 2011 All rights reserved ...
Страница 112: ... Ericsson AB 2011 All rights reserved ...
Страница 124: ... Ericsson AB 2011 All rights reserved ...
Страница 130: ...editable Ericsson AB 2011 All rights reserved ...
Страница 145: ... Ericsson AB 2011 All rights reserved ...
Страница 148: ......
Страница 161: ...alarms All traps i e start up events and all alarms and warnings Ericsson AB 2011 All rights reserved ...
Страница 170: ......
Страница 211: ... Ericsson AB 2011 All rights reserved ...
Страница 220: ... Ericsson AB 2011 All rights reserved ...
Страница 225: ... Ericsson AB 2011 All rights reserved ...
Страница 245: ...Home SPR1100 Handbook Appendices Alarm Lists Alarm Lists Base Unit MPM1 Ericsson AB 2011 All rights reserved ...