#286-5489 Byrne Rd., Burnaby, BC, V5J3J1, Canada Phone: 888-387-3787 or 604-266-8547 www.equustek.com
22
3.
The configuration for the Modbus
Slave
is different than the Modbus
Master
. Follow
the instructions for the mode that the mode that the DL6000 will be configured for.
5.3.1.1 Modbus Slave Parameters
4.
For the
Modbus Device Type
, select
Slave
to bring up the configurable slave
parameters.
5.
Select the Allan-Bradley PLC type. There are 3 choices available, PLC-5, PLC-3,
and SLC/Micrologix/ControlLogix. Unless you need to communicate to a PLC-3, we
suggest that you use the SLC/Micrologix/ControlLogix option as the PLC type.
6.
Select whether broadcast messages are to be forwarded or not. The default option is
to
not
forward broadcast messages. If broadcast messages are to be forwarded, you
will then be prompted to select the address range of devices on the DH+ that will
have the broadcast messages forwarded to them.
7.
Click the
Next
button to setup the Modbus to Allan-Bradley mapping table. A new
window will appear as shown below.