Equflow 6010BCPM Pulse Input Batch Controller Instruction Manual
6
Multi-Point
Linearization
2 to 32 points
Low-Flow
Cutoff
0-999999 (0 disables cutoff function)
Decimal Point
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
,
or
dddddd
Calibration
May be calibrated using K-factor, internal
calibration, or by applying an external
calibration signal.
K-Factor
Field programmable K-factor converts input
pulses to rate in engineering units. May be
programmed from 0.00001 to 999,999
pulses/unit.
Calibration
Range
Input 1 signal may be set anywhere in the
range of the controller; input 2 signal may be
set anywhere above or below input 1 setting.
Minimum input span between any two inputs
is 10 Hz.
An error message will appear if the input 1
and input 2 signals are too close together.
Filter
Programmable contact de-bounce filter: 40
to 999 Hz maximum input frequency allowed
with low speed filter.
Time Base
Second, minute, hour, or day
Gate
Low gate: 0.1-99.9 seconds
High gate: 2.0-999.9 seconds
F4 Digital
Input
Contacts
3.3 VDC on contact. Connect normally open
contacts across F4 to COM.
F4 Digital
Input
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Batch Controller Rate/Totalizer Display
Rate Display
Indication
-
99999 to 999999, lead zero blanking. “R”
LED illuminates while displaying rate.
Batch Total &
Grand Total
Display
0 to 999,999; automatic lead zero blanking.
“T” LED is illuminated while displaying batch
total.
“GT” LEDs are illuminated while
displaying grand total. Up to 999,999 for
batch total/preset. Up to 999,999,999 with
grand total-
overflow feature. “
oF
” is displayed
to the left of grand total overflow and
▲ LED
is illuminated.
Batch Total
Decimal Point
Up to five decimal places or none:
d
.
ddddd
,
d
.
dddd
,
d
.
ddd
,
d
.
dd
,
d
.
d
,
or
dddddd
Total decimal point is independent of rate
decimal point.
Totalizer
Calculates total based on rate and field
programmable multiplier to display total in
engineering units. Time base must be
selected according to the time units in which
the rate is displayed.
Grand
Totalizer
Rollover
Grand totalizer rolls over when display
exceeds 999,999,999. Relay status reflects
display.
Grand Total
Alarms
Up to seven, user selectable under setup
menu. Any set point can be assigned to
grand total and may be programmed
anywhere in the range of the controller for
grand total alarm indication. Relay 1 should
always be assigned to batch.
Programmabl
e Delay on
Release
0.1 and 999.9 seconds; applied to the first
relay assigned
to total or grand total.
If the controller is programmed to reset total
to zero automatically when the preset is
reached, then a delay will occur before the
total is reset.
Grand Total
Reset
Via front panel button, external contact
closure on digital inputs, automatically via
user selectable preset value and time delay,
or through serial communications.
Grand Total
Reset
Password
Grand total passwords may be entered to
prevent resetting the grand total from the
front panel.
Non-
Resettable
Grand Total
The grand total can be programmed as a
non-resettable total by entering the
password “050873”.
Caution!
Once the Grand Total has been
programmed as “non-resettable”
the feature cannot be disabled.
Relays
Rating
2 SPDT (Form C) internal; rated 3 A @ 30
VDC and 125/250 VAC resistive load; 1/14
HP (
≈
50 W) @ 125/250 VAC for inductive
loads
Noise
Suppression
Noise suppression is recommended for each
relay contact switching inductive loads; see
page 13 for details.
Relay
Assignment
Relays may be assigned to batch control
total, sampling, rate, or grand total alarms.
Preclose
0-100% of batch size, individually user
programmable for each additional batch
control relay beyond the first.
Alarm
Deadband
0-100% of span, user programmable
High or Low
Alarm
User may program any alarm for high or low
trip point.
Unused alarm LEDs and relays may be
disabled (turn off).
Relay
Operation
Batch control
Automatic (non-latching)
1
Sampling
Off (disable unused relays and enable
Interlock feature)
Manual on/off control mode
Secondary Functions
2
Latching (requires manual acknowledge)
!