Connect the individual components to the symbols provided, they are 

solar panel, battery and loads in order. Only install the regulator near the 
battery on a suitable surface. This surface should be solid, stable, even, 
dry and nonflammable. The battery cable should be as short as possible 
(1-2m) and have a suitable cable diameter size to minimize loss, e.g. use 

2.5mm

2

 

 

at 10A; use 4mm

2

 

 

at 20A. 

Observe the following connection sequence during commissioning

 

1)  Mount  the  controller  to  a  vertical  surface.  Allow  space  above  and 

below  the  controller  for  air  flow.  Note:  the  mounted  ambient 
temperature should not be over the working temperature of controller

-10

~60

℃)

 

2.Connect the po of battery to the fuse

and then connect the battery 

to the controller. The current of fuse should be chosen 3-4 times of rated 
current. Note the plus and minus.   

3.  Connect  the  photovoltaic  module  to  the  charge  regulator

  - 

plus  and 

minus 

4. Connect the consumer to the charge regulator

 

plus and minus 

Please observe that the automatic adjustment to 12V/24V   

systems  does  not  function  properly,  if  this  sequence  order  is  not 

followed. An improper sequence order can damage the battery!   

5.The parameters can be set depending on 

the user’s need. 

6.The negative battery is grounded or ground connected as the above.   

4. Operation & instructions: 

Keys & instructions(from left to right)

 

 

K1

Reading  status,  switch  to  next  figure

Setting  status,  switch  to  next 

function or increase the setting data. 

K2

Reading status, switch to the previous figure; setting status, switch to 

the previous function or decrease the setting data.   

K3: On reading status, press K3, then on setting status; on setting status, 

press K3, and save the data, back to reading status. 

K4

Cancel/power switch, on setting status, no saving with K4. On reading 

status,  K4  is  power  switch  while  loads  are  working.  Recovery  key 
while it’s short

circuited or over load(with ON/OFF mode). 

 

Display instructions: LCD display as the setting mark: 

1

  sun  symbol, 

  on  is  daytime  and 

on  is  night  time

flashing shows over voltage.   

  2

Charging mode

. PWM charging   

3

  battery. The strips inside show the status of charging or 

discharging and current capacity percentage. 

 

If discharging, the strips will reduce. 

 

       

 

 

 

 

 

 

 

 

 

     

System assembly 

 

 

 


+        - 

-

 

Solar    Module 

Battery 

Fuse 

Load 

           

 

 

Load symbol 

   

Battery status 

 

 

 

 

               

 

 

           

 

 

 

 

Содержание EPIP20-LT Series

Страница 1: ...t equalizing float charging Four work mode ON OFF lighting control Lighting hours on ON OFF exact time Protecting Function TVS lighting protecting Over load short circuit polarity reverse protection electronic fuse Display LCD display specially designing for solar system LCD display all system parameters in digital value system status as symbols Accurate clock show 2 Controller panel instructions ...

Страница 2: ...tems does not function properly if this sequence order is not followed An improper sequence order can damage the battery 5 The parameters can be set depending on the user s need 6 The negative battery is grounded or ground connected as the above 4 Operation instructions 1 Keys instructions from left to right K1 Reading status switch to next figure Setting status switch to next function or increase...

Страница 3: ... Operation instructions 4 1 Reading specifications On reading status press K1 K2 LCD will repeat the following specifications 4 3Battery capacity modify While display battery capacity XXXX AH press K3 into setting mode battery unit AH SET is flashing modify the data through K1 K2 press one time battery capacity will be up down 10 the maximum is 5000 the minimum is 50 Press K3 for saving or K4 for ...

Страница 4: ...ws the display order Press K3 SET and H of H M flashes user can modify hours by K1 K2 Press K3 to confirm the modification and save the data and return to the fourth step Press K4 to cancel the modification and return to the fourth step and SET stop flashing When modify Hour and Minute H will be modified first Press K3 and turn to M modification Press K3 again confirm the modification and save the...

Страница 5: ...on 1 25 times of Ie for 60secs 1 5 times of Ie by for 5secs overload protection 3 time of Ie short circuit protection Self consumption Control mode 15 mA LED LCD display 15mA Total 30mA System voltage 12 24V AUTOWORK Work temperature industrial 20 to 70 Battery capacity Battery in parallel from 50AH to 5000ah Boost charging 14 8V 2 24V equalizing charging voltage 14 4V 2 24V Float charging 13 6V 2...

Отзывы: