press the switch to reset the controller immediately.
While the over load occurs within 20s, press the switch and the load will be
reconnected after 10s.
While the over load occurs over 20s, press the switch and the load will be
reconnected immediately.
2. After over discharged, the load will be reconnected automatically when
the battery is charged to 13.1V. (For 12V system only, for 24V, it is 26.2V)
After over discharged, the load will be reconnected while you press the
power switch. Please note the battery voltage needs to be over 12.5V. (For
12V system only, for 24V, it is 25V. )
To correct problem
1.
Check wires
2.
Reduce amps if needed
3.
Reset controller
Disconnect battery +
Reconnect battery
+
RATINGS (12V or 12/24V auto work)
EPHC10-EC 170W or 10 A for Solar and Load
NOTES: For use with solar panels only
TECHNICAL INFORMATION
Equalization voltage (60 minutes)
14.8 V
Boost voltage (60 minutes)
14.4 V
Float Voltage 13.7V
Low voltage Disconnect
11.1 V
Low voltage Reconnect 13.1 V
Note: all is for 12V system only, use 2x for 24 V system