Epsolar EPHC10-EC series Скачать руководство пользователя страница 2

                                                                 

  LED indicator 

 

Green ON when solar is charging battery 

Gree

n blink when the system over voltage 

 

                                                                                                   

 

  Green ON when battery level in the right range 

 

Green slowly flashing when battery level full 

  Yellow ON when battery level low 

                          Red ON when loads cut off 

 

Red slowly flashing when it’s over load 

(The load amps is 1.25 times of rated current for 60 seconds,   

or the load amps is 1.5 times of rated current for 5 seconds)   

                          Red fast flashing when the load is short-circuit.   

 

      Red ON when the switch is ON. 

      Red OFF when the switch is OFF.   

      The default status is ON 

 

Please note:   

1.

 

The output will be cut off once there is over load or short circuit. 

While short circuit occurs, the controller will have 4 automatic loads 

reconnect attempts. There will be 10s between the first three attempts and 

20s between the 3

rd

 and 4

th

 attempts. For the fifth short circuit, the load 

can be only reconnected after 24hours.Anytime, please check the load and 