1.7.5
Alarm signals
The equipment offers various possibilities for signaling alarm conditions, however, not for danger situations. The
signals may be optical (on the display as text), acoustic (piezo buzzer) or electronic (status output of the analog
interface or digitally readable status bits). All alarms will cause the device to switch off the DC output.
The meaning of the signals is as follows:
Signal
OT
(OverTemperature)
•
Overheating of the device
•
DC output will be switched off
•
Non-critical
Signal
OVP / SOVP
(OverVoltage)
•
Overvoltage shutdown of the DC output due to excess of the preset limit
•
Critical! The device and/or the load could be damaged
Signal
OCP
(OverCurrent)
•
Shutdown of the DC output due to excess of the preset limit
•
Non-critical, protects the load from excessive current consumption
Signal
OPP
(OverPower)
•
Shutdown of the DC output due to excess of the preset limit
•
Non-critical, protects the load from excessive power consumption
Signal
PF
(Power Fail)
•
DC output shutdown due to AC undervoltage or defect in the AC input
•
Critical on overvoltage! AC input circuit could be damaged
Signal
MSP
(Master-Slave Pro
-
tection)
•
DC output shutdown due to communication problems on the master-slave bus
•
Non-critical
Signal
SF
(Share Bus Fail)
•
DC output shutdown due to signal distortion on the Share bus
•
Non-critical
1.8
Technical data
1.8.1
Approved operating conditions
•
Use only inside dry buildings
•
Ambient temperature 0-50°C (32...122°F)
•
Operational altitude: max. 2000 m (6500 ft) above sea level
•
Max 80% relative humidity, not condensing
1.8.2
General technical data
Display:
Color TFT touch screen with gorilla glass, 5”, 800pt x 480pt, capacitive
Controls:
2 rotary knobs with pushbutton function, 1 pushbutton
The nominal values for the device determine the maximum adjustable ranges.