820-0003
IPES IR3 Flame Detector
Operating Manual
Page
29
of
37
14.0 Certifications
The IPES
–
IR3 meets the following certifications:
FM (U.S. &
Canada)
Hazardous
Locations
Zone Locations
Class I, Division 1, Groups B, C & D,
T4, Ta = ‐4
0
o
C to +85
o
C (‐40
o
F to
+185
o
F) IP66
Class I, Zone 1, AEx d IIC, T4, Gb
1.
ISO Class 12.9, M5 X 20 socket‐head cap screws (Yield Stress 1100 MPa) shall be
used to replace the cover fasteners.
2.
ISO Class 12.9, M5 X
25 socket‐head ca
p screws (Yield Stress 1100 MPa) shall be
used to replace the base fasteners.
Fire Protection
Approval Standards: FM3260 (2000); FM3600 (1998); FM3615 (2006); ANSI/ISA
60079‐0
Equipment
(2009); ANSI/ISA
60079‐1
(2009);
CAN/CSA‐C22.2
No.
60079‐0
(2007); CAN/C
SA‐C22.2
No.
60079‐1
(2007)
Supporting Standards: ANSI/FM3260 (2004); ANSI/NFPA 72 (2002); ULC/ORD
–
C386 (1990);
CAN/ULC
–
S529 (2002); CSA C22.2 No. 0.5 (reaffirmed 1999); C22.2 No. 32 (reaffirmed 2003);
ANSI/IEC 60529 (2004)
; CSA‐C22.2 No.
60259 (2005)
ABS
Class I, Division 1, Groups B, C & D,
T4 Ta = ‐40
o
C to +85
o
C (‐40
o
F to
+185
o
F) IP66
ATEX/CE
Flameproof
“d”
Ex d IIC T4 Gb Ta = ‐40
o
F to +185
o
F (‐40
o
C to +85
o
C)
Supporting Standards: EN 60079‐0:2009; EN 60079‐1:2007
ATEX Certificate Number: FM11ATEX0045X
Specific Conditions of Use:
1.
ISO Class A2‐70, M5 X 16 socket‐head cap screws (Yield Stress 450 MPa) shall
be
used to replace the cover fasteners.
2.
ISO Class A2‐70, M5 X 16 socket‐head cap screws (Yield Stress 450 MPa) sh
all be
used to replace the base fasteners.
3.
Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
Certificate of Conformity: CE Mark for EMC (TUV)
CE Mark for ATEX
IP66