Installation Guide
Information Label on each tank
Use of drip trays for installations over ceiling height is HIGHLY recommended
›
Customer/installer to check unit for any
damage or leaks on delivery prior to
installation of unit
›
Bunded tank or tank with drip tray
should be used for in-house installations
(depending on tank application & location)
›
Tank installation above ceiling level is not
recommended. Unit’s ideal support base
is concrete due to weight. (i.e. 1L of water
= 1 kg)
›
Unit to be fi tted in a safe place away from
any potential hazards & kept out of direct
sunlight
›
Protective lid of tank to be installed over
control unit
›
EPS is unable to service any unit installed
above ceiling level unless in accordance
with H&S regulations
›
Unit to be installed by qualifi ed persons
only
›
EPS recommends a by-pass valve be fi tted
on both the inlet & outlet in the unlikely
event of a pump failure
›
Isolation shut-off valve to be fi tted
on supply & delivery side of tank (for
maintenance purposes
DO NOT REMOVE THIS LABEL
(Removal of this label will void warranty)
Inlet
Overfl ow
By-Pass Line
Typical example of installation
Rethinking
Water
›
The overfl ow pipe that is fi tted should be
twice the size of the inlet supply minimum (it
may have to be enlarged further, depending
on incoming pressure and fl ow) and should
be piped away to safe drainage zone. (It’s
recommended that a full test is carried out by
the installer).
›
Overfl ow test to be completed after every
installation. This is to ensure the capacity of the
overfl ow pipe is able to handle any ballcock
failure, blockage or restriction. Ensure pipe is
not restricted & is laid straight with a suffi
cient
fall without lags.
›
The overfl ow pipe must not be obstructed or
restricted (no sharp elbows), factoring in the
distance being piped away to the drainage zone.
›
Overfl ow/vermin screen needs to be cleaned
regularly to ensure removal of any impurities
present in the water.
›
Pressure vessel air pre-charge to be checked
every 6 months (set 2lbs below cut-in pressure)
›
High pressure ballcock fi tted as standard. (Low
range available on request)
›
EPS recommends testing water for any
impurities or any water treatment required
›
EPS accept no responsibility whatsoever for leaks
inside /outside of tank which are outside of our
control
ASSEMBLED BY:
DATE:
INSTALLED BY:
DATE:
TEL:
MULTI
BOOST
Scan for O&M Manual
or download on
Multiboost.ie
Scan for Multiboost O&M Manual
or download at Multiboost.ie
Fitting of a bypass unit & drip tray
with correct overflow capability is
highly recommended
Full overflow test
is necessary
on
every installation
Use of sharp elbows that may cause
flow restrictions is not recommended
The
MULTI
BOOST
Range
C
M
Y
CM
MY
CY
CMY
K