PS 5000 A Series

3.4.4 

Manually configure protections

Along with adjustable set values, the device offers excess protections related to voltage, current and power, which 

are intended to protect the possibly expensive load hardware. They are configurable in form of adjustable thresh

-

olds that the device supervises and in case of excess it will switch off the DC output. Those protections are OVP 

(overvoltage protection), OCP (overcurrent protection) and OPP (overpower protection). Any of these values is 

adjustable between 0% and 110% of the related nominal value.
The thresholds are manually adjustable at any time. There is a dedicated mode OVP/OCP which can be accessed 

via the equally named pushbutton.
The control panel lock (see 

3.4.7

) can block the user from adjusting the thresholds.

 

How to manually adjust the thresholds of OVP and OCP

1. 

In normal operation, push button 

OVP/OCP

 once to enter OVP/OCP 

adjustment mode

2. 

The display switches to show the OVP and OCP thresholds, as indicated 

in the example screenshot to the right.

3. 

Adjust those values as desired, like when adjusting voltage or current. 

The adjustment range here is 10% bigger so the thresholds can also 

be adjusted above the maximum voltage or current.

4. 

Leave this adjustment mode by pressing button 

OVP/OCP

 again.

 

How to manually adjust the threshold of OPP

1. 

In normal operation, press button 

OVP/OCP

 once. After this, push 

both

 

rotary knobs 

simultaneously

 to enter OPP adjustment mode. This 

mode can also be reached by doing it vice versa, means first to push 

both knobs and then pushbutton 

OVP/OCP

.

2. 

The display switches to show the OPP threshold (unit W), as indicated 

in the example screenshot to the right.

3. 

Adjust the value like you would adjust the power set value. The adjustment range here is 10% bigger so the 

threshold can also be adjusted above the maximum power.

4. 

Leave this adjustment mode again by pressing button 

OVP/OCP

 and then pushing both rotary knobs si-

multaneously. Or do it vice versa.

With the DC output being switched on, the thresholds immediately become effective while 

adjusting and they might generate an alarm, in case any of these three thresholds is adjusted 

lower than the related set value.

The value OVP and OCP are part of the recall sets (see 3.4.6), the value OPP is not.

3.4.5  Switching the DC output on or off

The DC output of the device can be manually or remotely switched on and off. Switching it on can be restricted in 

manual operation by the control panel being locked (see 

3.4.7

), whereas switching it off manually is always pos-

sible for safety reasons, unless the device is in remote control.

 

How to manually switch the DC output on or off

1. 

As long as remote control is not active, push button 

On/Off 

anytime to switch the DC output off, in case it is 

on. As long as the control panel (HMI) is not locked, press the button anytime to switch the DC output on, 

in case it is off.

2. 

The button toggles between the two states, as long as a change is not restricted by an alarm or the device 

being in “remote” mode. The current condition is displayed as “On” or “Off”.

 

How to remotely switch the DC output on or off via the digital interface

1. 

See the external documentation “Programming Guide ModBus & SCPI” if you are using custom software, 

or refer to the external documentation of LabView VIs or other software provided by the manufacturer.

Содержание PS 5040-10 A

Страница 1: ...E P S S t r o m v e r s o r g u n g Doc ID PS5EN Revision 05 Date 01 2017 Operating Guide PS 5000 A DC Laboratory Power Supply...

Страница 2: ......

Страница 3: ...nection of remote sensing 23 2 3 7 Connecting the USB port rear side 24 2 3 8 Initial commission 25 2 3 9 Commission after a firmware update or a long period of non use 25 3 OPERATIONANDAPPLICATION 3...

Страница 4: ...ety notices as well as general notices in this document are shown in a box with a symbol as follows Symbol for a life threatening danger Symbol for general safety notices instructions and damage prote...

Страница 5: ...current of the device in Ampere Maximum voltage of the device in Volt Series 5 Series 5000 Type identification PS Power Supply usually programmable PSI Power Supply Intelligent always programmable ELR...

Страница 6: ...ccur which can cause burns as well as damage to the equipment and to the user For electronic loads do not connect power sources to equipment under power sparking may occur which can cause burns as wel...

Страница 7: ...responsibilities for operation maintenance and cleaning of the equipment ensure that all employees who use the equipment have read and understood the manual Furthermore the users are to be regularly s...

Страница 8: ...or the load could be damaged Signal OCP OverCurrent Shutdown of the DC output due to excess of the preset limit Non critical protects the load from excessive current consumption Signal OPP OverPower...

Страница 9: ...0 2 UNom 0 2 UNom 0 2 UNom Ripple 2 40 mVPP 5 mVRMS 80 mVPP 10 mVRMS 150 mVPP 30 mVRMS Remote sensing compensation Max 6 UNom Max 6 UNom Max 6 UNom Current regulation Adjustment range 0 10 2 A 0 5 1 A...

Страница 10: ...inlet rear exhaust Ambient temperature 0 50 C Storage temperature 20 70 C Humidity 80 not condensing Standards EN 61010 EN 61326 Overvoltage category 2 Protection class 1 Pollution degree 2 Operation...

Страница 11: ...UNom 0 2 UNom Ripple 2 40 mVPP 5 mVRMS 80 mVPP 10 mVRMS 150 mVPP 30 mVRMS Remote sensing compensation Max 6 UNom Max 6 UNom Max 6 UNom Current regulation Adjustment range 0 20 4 A 0 10 2 A 0 4 08 A A...

Страница 12: ...inlet rear exhaust Ambient temperature 0 50 C Storage temperature 20 70 C Humidity 80 not condensing Standards EN 61010 EN 61326 Overvoltage category 2 Protection class 1 Pollution degree 2 Operation...

Страница 13: ...lay Accuracy 4 0 2 UNom 0 2 UNom 0 2 UNom Ripple 2 40 mVPP 5 mVRMS 80 mVPP 10 mVRMS 150 mVPP 30 mVRMS Remote sensing compensation Max 6 UNom Max 6 UNom Max 6 UNom Current regulation Adjustment range 0...

Страница 14: ...let rear exhaust Ambient temperature 0 50 C Storage temperature 20 70 C Humidity 80 not condensing Standards EN 61010 EN 61326 Overvoltage category 2 Protection class 1 Pollution degree 2 Operational...

Страница 15: ...any Fon 49 821 570451 0 Fax 49 821 570451 25 www eps germany de info eps germany de PS 5000 A Series Figure 1 Front side Figure 2 Back side 1 8 4 Views A Mains switch B Control panel C DC output D Exh...

Страница 16: ...bH Alter Postweg 101 86159Augsburg Germany Fon 49 821 570451 0 Fax 49 821 570451 25 www eps germany de info eps germany de PS 5000 A Series Figure 3 Right hand side view 640 W model Figure 4 Right han...

Страница 17: ...Button OVP OCP Switches to adjustment of OVP OCP and OPP values Button Local Activation deactivation of the remote control inhibit see 3 5 2 Button Lock Activation deactivation of the control panel l...

Страница 18: ...ut Series or parallel connection are possible The DC output clamps on the front are suitable to connect soldered cable ends spade lugs cable end sleeves or 4mm B schel plugs All models are controlled...

Страница 19: ...ssigned either to the output voltage and related parameter OVP or the power and the related parameter OPP whereas the right hand rotary knobs is always assigned to the output current and related param...

Страница 20: ...00 V 4 0 1 V 10 A 20 A 4 0 01 A 320 W 4 0 1 W 40 A 4 0 01 A 640 W 4 0 1 W In manual operation every set value can be set in the increments given above In this case the actual output values set by the...

Страница 21: ...note and or parts list see section 1 9 2 Scope of delivery An obviously damaged device e g loose parts inside damage outside must under no circumstances be put in operation 2 3 Installation 2 3 1 Prep...

Страница 22: ...auxiliary outputs and then connecting the load on one of the main outputs on the front unless the total current does not exceed 32 A With the 40 A model it is not allowed to use and plug 4mm B schel p...

Страница 23: ...6 Connection of remote sensing In order to compensate to a certain degree the voltage loss in a DC cable the device provides the possibility to connect the remote sensing input Sense to the load The...

Страница 24: ...C device and is usually integrated in current operating systems such as Windows 7 or 10 But it is strongly recommended to use and install the included driver installer on USB stick to gain maximum com...

Страница 25: ...settings for set values safety and monitoring functions and communication are suitable for your application and change them where necessary as described in the manual In case of remote control via PC...

Страница 26: ...2 Current regulation constant current current limiting Current regulation is also known as current limitation or constant current mode CC The DC output current is held constant by the power supply onc...

Страница 27: ...switch off the DC output and can occur if the power supply itself as a voltage source generates an output voltage higher than set for the overvoltage alarm limit OVP 0 110 UNom or the connected load s...

Страница 28: ...ode the middle row shows the set values The power set value is not directly adjustable from here The control panel lock see 3 4 7 can block the user from adjusting set values How to adjust voltage and...

Страница 29: ...ing it vice versa means first to push both knobs and then pushbutton OVP OCP 2 The display switches to show the OPP threshold unit W as indicated in the example screenshot to the right 3 Adjust the va...

Страница 30: ...the former values won t be overwritten After using any of these two buttons recall mode is left After the desired number of presets have been defined to custom needs they can be recalled and used How...

Страница 31: ...bited condition the status Local will be displayed lower row of the display See example screenshot to the right Activating the inhibit can be useful if the device is remotely controlled by software or...

Страница 32: ...caused by the device being faulty or by an external source The DC output will be switched off 0 V 1 1 UNom OCP OverCurrent Protection Triggers an alarm if the DC output current reaches the defined thr...

Страница 33: ...pole of any unit in the series connection must have a potential of 200 V against ground PE Remote sensing must not be wired to the load only the sense bridges on the aux output rear are allowed Serie...

Страница 34: ...n is abroad the necessary customs papers are attached 4 2 1 Replacing a defect mains fuse The device is protected by one 5x20 mm fuse T16 A 250 V which is located on the rear of the device inside a fu...

Страница 35: ......

Страница 36: ......

Отзывы: