15
CAUTION
If the power is supplied to the different AC loads, it is suggested to turn on the loads
with a larger surge current till the load works well, then turn on the loads with a
smaller surge current. Especially for inductive loads, they should be turned on one by
one. Do not turn on the loads simultaneously to not cause excessive impact to the
inverter, to shorten its life span.
If the inverter is not in regular operation, or LCD or indicator displays abnormal, refer
to Section 5 to clear the fault or contact the after-sale service personnel of our
company.
Step12: Power off the equipment
1. Disconnect the AC load circuit breaker.
2. Long press the "AC output" button to turn off the inverter output.
3. Disconnect the bypass circuit breaker.
4. Disconnect the battery circuit breaker.
WARNING
As electricity exists in the capacitance, the LCD screen would be off after 30 seconds;
wait 5 minutes before opening the equipment to repair.
The inverter has a soft stat design and only takes effect when it starts. Do not
frequently switch the input circuit breaker when the inverter is incompletely powered
off. Otherwise, the input battery would undergo a high current impact. That is, the
input circuit breaker can be closed again after the LCD screen is off.
WARNING
After the inverter is disconnected from the utility and battery bank, you must wait 5
minutes before touching the internal conductive devices.
2.4 Output voltage/frequency grade switch
Operating steps:
Open the cover plate on the inverter right side and find the dial switches on the control board, located
on the top left corner; see the picture above. Set the output voltage/frequency according to demand,
then restart the inverter to take effect.
IMPORTANT
The factory default output voltage is 220VAC, and the output frequency is 50Hz.
The accessories can refer to the Packing List.
When the dial switch 1 is placed to the ON side, the output frequency is
60Hz, otherwise it is 50Hz,
When the dial switch 2 is placed to the ON side, the output voltage is
230VAC, otherwise it is 220VAC.
Содержание TP10K
Страница 1: ...Pure Sine Wave Inverter User Manual Models TP10K TP10KB TP20K TP20KB TP30K TP30KB TP40K TP40KB...
Страница 2: ......
Страница 12: ...9 1 5 Electrical schematic diagram...
Страница 15: ...12 Step3 Takedown the junction box cover plate with special tools Step4 Wiring...
Страница 34: ...31 TP30K TP30KB TP40K TP40KB 40KW 26KW 1500M 5000M PO H 0...
Страница 36: ...33 Annex 2 Mechanical Dimension Diagram 1 TP10K TP10KB...
Страница 37: ...34 2 TP20K TP20KB...
Страница 38: ...35 3 TP30K TP30KB...
Страница 39: ...36 4 TP40K TP40KB Any changes without prior notice Version number V2 1...