background image

 

 

 

Pure Sine Wave Inverter 

 

User Manual

 

Models: 

TP10K/TP10KB 

TP20K/TP20KB 

TP30K/TP30KB 

TP40K/TP40KB 

 

Содержание TP10K

Страница 1: ...Pure Sine Wave Inverter User Manual Models TP10K TP10KB TP20K TP20KB TP30K TP30KB TP40K TP40KB...

Страница 2: ......

Страница 3: ...c diagram 9 2 Installation 10 2 1 Warning 10 2 2 Wire breaker selection 10 2 3 Instructions 11 2 4 Output voltage frequency grade switch 15 3 Interface 16 3 1 Indicator 16 3 2 Buzzer 17 3 3 Buttons 17...

Страница 4: ...Indicate any practical advice for reference IMPORTANT Indicates a critical tip during the operation if ignored may cause the device to run in error CAUTION Indicates potential hazards if not avoided...

Страница 5: ...prohibited to connect multiple units output in parallel or series otherwise the inverter would be damaged 5 Safety cautions for mechanical installation WARNING Before installation must make sure the...

Страница 6: ...vices could be touched The inverter can be restarted after removing the faults which may affect its safety performance There are no maintenance parts in the inverter please contact our after sales ser...

Страница 7: ...l rotary caster is optional for the system which contains lifting support feet to fix or move the inverter at any time and improve product mobility and flexibility Features Advanced SPWM technology an...

Страница 8: ...hapter 3 Junction box cover plate To cover the terminals and circuit breakers Pedestal To fixed the inverter Input output circuit breaker group Protective devices to safely cut off the current Input O...

Страница 9: ...ry input terminals AC output breaker Bypass input terminals Remote switch RS485 communication port Remote switch RS485 communication port pin definitions 1 Red 2 White ON OFF 3 Yellow 5Vdc 4 Black GND...

Страница 10: ...s to 35 below IMPORTANT DC fans have the self checking function when the inverter is powered on The DC fans would automatically run for three seconds AC fan 3 pieces Inverter priority When the interna...

Страница 11: ...schematic diagram WARNING The AC equipment must be determined according to the output power of the inverter Do not connect the load exceeding the inverter s maximum input power Otherwise the inverter...

Страница 12: ...9 1 5 Electrical schematic diagram...

Страница 13: ...voltage exists inside the inverter after turning off the switch Do not open or touch the internal devices and wait five minutes before conducting related operations Please do not install the inverter...

Страница 14: ...d circuit breaker according to the practical situation 2 3 Instructions Installation steps Step1 Professional personnel read this manual carefully Step2 Determine the installation location and heat di...

Страница 15: ...12 Step3 Takedown the junction box cover plate with special tools Step4 Wiring...

Страница 16: ...ssive heat would accumulate at the connection points to damage the terminals or even cause a fire Danger high voltage Terminals of the Utility input AC output and DC input produce high voltage do not...

Страница 17: ...e inverter would start the output Method 2 Connect the remote switch short circuit cable 1 red cable 2 white of the remote switch and RS485 communication interface the inverter would start the output...

Страница 18: ...ment to repair The inverter has a soft stat design and only takes effect when it starts Do not frequently switch the input circuit breaker when the inverter is incompletely powered off Otherwise the i...

Страница 19: ...er OFF On Solid Inverter Priority Slowly Flashing 0 5Hz Inverter working Fast Flashing 2 5Hz Inverter fault Bypass Green OFF Bypass OFF On Solid Bypass Priority Slowly Flashing 0 5Hz Bypass working Fa...

Страница 20: ...he button and hold on 3s Switch the inverter and bypass mode Browse Press the button Browse the Utility Battery Load column parameters Press the button and hold on 3s Browse the Utility Battery Load c...

Страница 21: ...us Load parameters Voltage Current Power Frequency System running in inverter status 3 5 Icon Icon Instruction Icon Instruction No Utility connecting Load 25 Utility connecting Load 25 50 Inverter out...

Страница 22: ...and browse buttons for 3seconds together to clear the accumulated consumed electricity 4 Clear fault Operation Under failure state short press any button the buzzer would stop sounding but the failure...

Страница 23: ...nds in a long cycle Bypass works normally AC output continues When the input voltage backs to normal the fault warning stops Input low voltage protection Inverter mode DC input voltage is lower than t...

Страница 24: ...me delay for 15 seconds Suppose the IGBT over current state continues after three times auto recovery In that case the output will recover only when the fault is cleared and manually restart Radiator...

Страница 25: ...tch to bypass mode Bypass frequency abnormal Inverter mode Bypass input frequency exceeds the 50Hz 60Hz 10 Fault code BFA Buzzer sounds in long cycle The inverter works normally AC output continues Wh...

Страница 26: ...oltage rises to the rated input voltage Bypass mode 10S Inverter output troubleshooting Fault Fault Code Working mode LED indicators Buzzer Status Troubleshooting Output voltage abnormal OVA Fault ind...

Страница 27: ...ck whether the load is a short circuit 2 Five minutes after power off open the left side cover plate check whether the IGBT screw or wire connection is loose check whether the IGBT is broken Radiator...

Страница 28: ...istent with required Pay attention to any troubleshooting or error indication Take corrective action if necessary Confirm that all the terminals have no corrosion insulation damaged high temperature o...

Страница 29: ...oltage 220 230VAC 3 Battery power mode Output frequency 50Hz 60Hz 3 Battery power mode Output power factor 0 2 1 Output way Single phase Output wave Pure Sine Wave Output THD 3 Resistive load Max inve...

Страница 30: ...ut frequency 50Hz 60Hz 3 Battery power mode 50Hz 60Hz 3 Battery power mode Output power factor 0 2 1 Output way Single phase Output wave Pure Sine Wave Output THD 3 Resistive load Max inverter efficie...

Страница 31: ...x inverter efficiency 92 Resistive rated load Bypass Input voltage range 170VAC 275VAC Bypass transfer time 12mS No load consumption 2 Backlight 30S Turn on by pressing the button Mechanical Parameter...

Страница 32: ...29 TP10K TP10KB TP20K TP20KB 8 TP30K TP30KB 2 Temperature derating for TP40K TP40KB For each increase of 1 above 30 the output power is reduced by 750W...

Страница 33: ...30 40KW 25KW 30 50 PO T 25 3 Altitude derating For each increase of 500m above 1500m the output power is reduced by 5 of the rated power TP10K TP10KB TP20K TP20KB...

Страница 34: ...31 TP30K TP30KB TP40K TP40KB 40KW 26KW 1500M 5000M PO H 0...

Страница 35: ...rated value of the inverter Damage caused by the ambient temperature exceeds the limit working environment temperature The accident was caused by disobeying the marks or manuals of the inverter such...

Страница 36: ...33 Annex 2 Mechanical Dimension Diagram 1 TP10K TP10KB...

Страница 37: ...34 2 TP20K TP20KB...

Страница 38: ...35 3 TP30K TP30KB...

Страница 39: ...36 4 TP40K TP40KB Any changes without prior notice Version number V2 1...

Страница 40: ...HUIZHOU EPEVER TECHNOLOGY CO LTD Beijing Tel 86 10 82894896 82894112 Huizhou Tel 86 752 3889706 E mail info epever com Website www epever com...

Отзывы: