10
point voltage (V
mpp
) of the MPPT controller, the series number of different types
PV modules can be calculated. The below table is for reference only.
System
voltage
36cell
Voc
<
23V
48cell
Voc
<
31V
54cell
Voc
<
34V
60cell
Voc
<
38V
MAX.
Best
MAX.
Best
MAX.
Best
MAX.
Best
12V
4
2
2
1
2
1
2
1
24V
6
3
4
2
4
2
3
2
48V
6
5
4
3
4
3
3
3
System
voltage
72cell Voc
<
46V
96cell Voc
<
62V
Thin-Film
Module
Voc
>
80V
MAX.
Best
MAX.
Best
12V
2
1
1
1
1
24V
3
2
2
1
1
48V
3
2
2
2
1
NOTE
: The above parameter values are calculated under standard test
conditions (STC (Standard Test Condition)
:
Irradiance 1000W/m
2
,
Module
Temperature 25
℃,
Air Mass1.5.)
(2) PV array maximum power
This MPPT controller has a limiting function of charging current, the charging
current will be limited within rated range, therefore, the controller will charge
the battery with the rated charging power even if the input power at the PV
exceeds.
The actual operation power of the PV array conforms to the conditions below:
1
)
PV array actual power ≤ controller rated charge power, the controller
charge battery at actual maximum power point.
2
)
PV array actual power > controller rated charge power, the controller
charge battery at rated power.
If the PV array higher than rated power, the charging time at rated power to
battery will be longer, more energy to battery yields.
WARNING:
Controller will be damaged when the PV array straight
polarity and the actual operation power of the PV array is three times
greater than the rated charge power!
WARNING:
Controller will be damaged when the PV array reverse
polarity and the actual operation power of the PV array is 1.5 times
greater than the rated charge power!