16
6.2Wire size &breaker
Wiring and installation should comply with national and local electrical
requirements.
Wire, terminals and breaker selection for battery
Models
Battery wire
size
Ring
Terminal
Breaker
IP1500-12-Plus(T)
35mm
2
/1AWG
RNB38-6
DC
—100A
(2P in parallel)
IP2000-12-Plus(T)
50mm
2
/1/0AWG
RNB60-10
DC
—125A
(2P in parallel)
IP2000-22-Plus(T)
25mm
2
/3AWG
RNB22-6L
DC/2P
—125A
IP2000-42-Plus(T)
16mm
2
/6AWG
RNB22-6L
DC/2P
—63A
IP3000-12-Plus(T) 70mm
2
/3/0AWG
RNB60-10
DC
—125A
(3P in parallel)
Wire and breaker selection for AC output
Models
Wire size
Breaker
IP1500-12-Plus(T)
1.5mm
2
/15AWG
AC/2P
—10A
IP2000-12-Plus(T)
2.5mm
2
/13AWG
AC/2P
—16A
IP2000-22-Plus(T)
2.5mm
2
/13AWG
AC/2P
—16A
IP2000-42-Plus(T)
2.5mm
2
/13AWG
AC/2P
—16A
IP3000-12-Plus(T)
4mm
2
/11AWG
AC/2P
—25A
IMPORTANT: The wire size and terminal are for reference only,
use thicker wires to lower the voltage drop, and improve the system
performance when the distance between inverter and batter is far.
IMPORTANT: The above wire size and circuit breaker size are for
recommendation only, please choose suitable wire and circuit breaker
according to the practical situation.
6.3 Mounting
Installation steps
:
Step1
:
Professional personnel read this manual carefully.
Step2
:
Determination of installation location and heat-dissipation space.