Troubleshooting
PE
CON+
®
www.epa.de
46
of
48
9
Troubleshooting
9.1
All LEDs remain dark
Ensure that the phase and neutral connector are properly connected and that the device is
supplied with the required voltage.
For the
PE
CON+
®
IT
, all three phases must be connected.
A neutral connection is not provided/required.
9.2
Red LED is illuminated
Protective earth connection interrupted
Ensure that the connection between the PE connection on the device and the protective
earth system is adequately low-resistance.
PE
CON+
®
S1
/
S3
/
NVF-1
/
NVF-2
:
Check the assignment of phase and neutral conductor to make sure the L and N polarity
are not switched.
Network phases fault
PE
CON+
®
IT
:
Ensure that all three phases are connected to the device and that they carry the correct
voltage. The voltage difference between the individual phases must not exceed 10% by too
much.
9.3
Service address
Please contact our service department if you have any questions.